1-2

Installation/Wiring

Mount the drive upright on a flat, vertical and level surface.

Install on 35 mm DIN Rail.
or

Install with screws.

Table 1.A Screw Mounting Recommendations

Protect the cooling fan by avoiding dust or metallic particles.

Do not expose to a corrosive atmosphere.

Protect from moisture and direct sunlight.

Minimum Mounting Clearances

Refer to

Appendix B

for mounting dimensions.

Ambient Operating Temperatures

Table 1.B Enclosure and Clearance Requirements

Debris Protection

A plastic top panel is included with the drive. Install the panel to prevent
debris from falling through the vents of the drive housing during
installation. Remove the panel for IP 20/Open Type applications.

Mounting Considerations

Minimum Panel Thickness Screw Size

Mounting Torque

1.9 mm (0.0747 in.)

M4 (#8-32)

1.56-1.96 N-m (14-17 lb.-in.)

Ambient Temperature

Enclosure Rating

Minimum Mounting
Clearances

Minimum

Maximum

-10°C (14°F)

40°C (104°F)

IP 20/Open Type

Use Mounting Option A

IP 30/NEMA 1/UL Type 1

(1)

(1)

Rating requires installation of the PowerFlex 4 IP 30/NEMA 1/UL Type 1 option kit.

Use Mounting Option B

50°C (122°F) IP 20/Open Type

Use Mounting Option B

25 mm

(1.0 in.)

120 mm

(4.7 in.)

120 mm

(4.7 in.)

120 mm

(4.7 in.)

120 mm

(4.7 in.)

Mounting Option A

No clearance required between drives.

Mounting Option B

Closest object that

may restrict air flow

through the drive heat

sink and chassis