Programming and Parameters

A051 &
A052
Options
(Cont.)

13 “10V In Ctrl”

Selects 0-10V or ±10V control as the frequency reference.
Start source is not changed.

14 “20mA In Ctrl”

Selects 4-20mA control as the frequency reference. Start
source is not changed.

15 - 25

Reserved

26 “Anlg Invert”

Inverts the scaling of the analog input levels set in

A110

[Anlg In 0-10V Lo] and

A111

[Anlg In 0-10V Hi] or

A112

[Anlg In4-20mA Lo] and

A113

[Anlg In4-20mA Hi].

A055 [Relay Out Sel]

Related Parameter(s):

P033

,

A056

,

A092

Sets the condition that changes the state of the output relay contacts.

Options

0 “Ready/Fault”

(Default)

Relay changes state when power is applied. This indicates
that the drive is ready for operation. Relay returns drive to
shelf state when power is removed or a fault occurs.

1 “At Frequency”

Drive reaches commanded frequency.

2 “MotorRunning”

Motor is receiving power from the drive.

3 “Reverse”

Drive is commanded to run in reverse direction.

4 “Motor Overld”

Motor overload condition exists.

5 “Ramp Reg”

Ramp regulator is modifying the programmed accel/decel
times to avoid an overcurrent or overvoltage fault from
occurring.

6 “Above Freq”

Drive exceeds the frequency (Hz) value set in

A056

[Relay

Out Level].

7 “Above Cur”

Drive exceeds the current (% Amps) value set in

A056

[Relay

Out Level].

Important: Value for

A056

[Relay Out Level] must be entered

in percent of drive rated output current.

8 “Above DCVolt”

Drive exceeds the DC bus voltage value set in

A056

[Relay

Out Level].

9 “Retries Exst”

Value set in

A092

[Auto Rstrt Tries] is exceeded.

10 “Above Anlg V”

Analog input voltage (I/O Terminal 13) exceeds the value
set in

A056

[Relay Out Level].

This parameter setting can also be used to indicate a PTC
trip point when the input (I/O Terminal 13) is wired to a
PTC and external resistor.

Use A056 to set threshold.

11-19

Reserved

20 “ParamControl”

Enables the output to be controlled over network
communications by writing to

A056

[Relay Out Level].

(0 = Off, 1 = On.)

21 “NonRec Fault””

Value set in

A092

[Auto Rstrt Tries] is exceeded.