D013, Display group, Continued) – Rockwell Automation 22A PowerFlex 4 User Manual FRN 6.xx User Manual
Page 41: D012 [control source, D013 [contrl in status, Programming and parameters 3-5
Programming and Parameters
3-5
Display Group
(continued)
d012 [Control Source]
Related Parameter(s):
,
Displays the active source of the Start Command and Speed Command which are normally defined
by the settings of
[Start Source] and
[Speed Reference] but may be overridden by digital
inputs. Refer to the flowcharts on pages
and
for details.
Values
Default
Read Only
Min/Max:
0/9
Display:
1
Start Command
Digit 0
0 = Keypad
1 = 3-Wire
2 = 2-Wire
3 = 2-Wire Level Sensitive
4 = 2-Wire High Speed
5 = RS485 (DSI) Port
9 = Jog
Speed Command
Digit 1
0 = Drive Potentiometer
1 =
[Internal Freq]
2 = 0-10V Input/Remote Potentiometer
3 = 4-20mA Input
4 =
-
[Preset Freq x]
(
[Digital Inx Sel] must be set to 4)
5 = RS485 (DSI) Port
9 = Jog Freq
Reserved
Digit 2
Reserved
Digit 3
d013 [Contrl In Status]
Related Parameter(s):
,
Status of the control terminal block control inputs.
Important: Actual control commands may come from a source other than the control terminal block.
Values
Default
Read Only
Min/Max:
0/1
Display:
1
1 = Input Present, 0 = Input Not Present
Start / Run FWD Input (I/O Terminal 02)
Bit 0
Direction / Run REV Input (I/O Terminal 03)
Bit 1
Stop Input
(1)
(I/O Terminal 01)
Bit 2
(1)
The stop input must be present in order to start the drive.
When this bit is a 1 the drive can be started.
When this bit is a 0 the drive will stop.
Reserved
Bit 3