beautypg.com

A084, A088, Advanced program group – Rockwell Automation 22A PowerFlex 4 User Manual FRN 6.xx User Manual

Page 55: Continued), A084 [boost select, A088 [maximum voltage, Programming and parameters 3-19

background image

Programming and Parameters

3-19

Advanced Program Group

(continued)

A084 [Boost Select]

Related Parameter(s):

d004

,

P031

,

P032

Sets the boost voltage (% of

P031

[Motor NP Volts]) and redefines the Volts per Hz curve.

(1)

(1)

Drive may add additional voltage unless option 5 is selected.

Options

1 “30.0, VT”

Variable Torque

2 “35.0, VT”

3 “40.0, VT”

4 “45.0, VT”

5 “0.0 no IR”

Constant Torque

6 “0.0”

7 “2.5, CT”

[Default for 3.7kW
(5HP) Drives]

8 “5.0, CT” (Default)

9 “7.5, CT”

10 “10.0, CT”

11 “12.5, CT”

12 “15.0, CT”

13 “17.5, CT”

14 “20.0, CT”

% P032 [Motor NP Hertz]

% P031 [Motor NP Volts]

100

50

1/2 [Motor NP Volts]

1/2

[Motor NP Hertz]

4
3
2
1

0

50

100

Settings

5-14

A088 [Maximum Voltage]

Sets the highest voltage the drive will output.

Values

Default

Drive Rated Volts

Min/Max:

20/Drive Rated Volts

Display:

1 VAC