P037, Basic program group, Continued) – Rockwell Automation 22A PowerFlex 4 User Manual FRN 6.xx User Manual
Page 46: P037 [stop mode
3-10
Programming and Parameters
Basic Program Group
(continued)
P037 [Stop Mode]
Related Parameter(s):
Active stop mode for all stop sources [e.g. keypad, run forward (I/O Terminal 02), run reverse (I/O
Terminal 03), RS485 port] except as noted below.
Important: I/O Terminal 01 is always a coast to stop input except when
[Start Source] is set for
“3-Wire” control. When in three wire control, I/O Terminal 01 is controlled by
[Stop Mode].
Hardware Enable Circuitry
By default, I/O Terminal 01 is a coast to stop input. The status of the input is interpreted by drive
software. If the application requires the drive to be disabled without software interpretation, a “dedicat-
ed” hardware enable configuration can be utilized. This is accomplished by removing the ENBL
enable jumper on the control board. In this case, the drive will always coast to a stop regardless of the
settings of
[Start Source] and
[Stop Mode].
Options
0 “Ramp, CF”
(1)
(Default) Ramp to Stop. “Stop” command clears active fault.
1 “Coast, CF”
Coast to Stop. “Stop” command clears active fault.
2 “DC Brake, CF”
DC Injection Braking Stop. “Stop” command clears active
fault.
3 “DCBrkAuto,CF”
DC Injection Braking Stop with Auto Shutoff.
•
Standard DC Injection Braking for value set in
[DC
Brake Time].
OR
•
Drive shuts off if the drive detects that the motor is
stopped.
“Stop” command clears active fault.
4 “Ramp”
Ramp to Stop.
5 “Coast”
Coast to Stop.
6 “DC Brake”
DC Injection Braking Stop.
7 “DC BrakeAuto”
DC Injection Braking Stop with Auto Shutoff.
•
Standard DC Injection Braking for value set in
[DC
Brake Time].
OR
•
Drive shuts off if current limit is exceeded.
(1)
Stop input also clears active fault.