A110, A111, A112 – Rockwell Automation 22A PowerFlex 4 User Manual FRN 6.xx User Manual
Page 61: A113
Programming and Parameters
3-25
A110 [Anlg In 0-10V Lo]
Related Parameter(s):
,
,
Sets the analog input level that corresponds to
[Minimum Freq] if a 0-10V input is used by P038
[Speed Reference].
Analog inversion can be accomplished by setting this value larger than
[Anlg In 0-10V Hi] or by
setting
-
[Digital Inx Sel] to option 26 “Anlg Invert”
Values
Default
0.0%
Min/Max:
0.0/100.0%
Display:
0.1%
0
P035 [Maximum Freq]
P034 [Minimum Freq]
A110 [Anlg In 0-10V Lo]
A111 [Anlg In 0-10V Hi]
0
Speed Reference
A111 [Anlg In 0-10V Hi]
Related Parameter(s):
,
,
Sets the analog input level that corresponds to
[Maximum Freq] if a 0-10V input is used by P038
[Speed Reference].
Analog inversion can be accomplished by setting this value smaller than
[Anlg 0-10V In Lo] or by
setting
-
[Digital Inx Sel] to option 26 “Anlg Invert”.
Values
Default
100.0%
Min/Max:
0.0/100.0%
Display:
0.1%
A112 [Anlg In4-20mA Lo]
Related Parameter(s):
,
,
Sets the analog input level that corresponds to
[Minimum Freq] if a 4-20mA input is used by
P038 [Speed Reference].
Analog inversion can be accomplished by setting this value larger than
[Anlg In4-20mA Hi] or by
setting
-
[Digital Inx Sel] to option 26 “Anlg Invert”.
Values
Default
0.0%
Min/Max:
0.0/100.0%
Display:
0.1%
A113 [Anlg In4-20mA Hi]
Related Parameter(s):
,
,
Sets the analog input level that corresponds to
[Maximum Freq] if a 4-20mA input is used by
P038 [Speed Reference].
Analog inversion can be accomplished by setting this value smaller than
by setting
[Digital Inx Sel] to option 26 “Anlg Invert”.
Values
Default
100.0%
Min/Max:
0.0/100.0%
Display:
0.1%