Specifications

Drive Ratings

Catalog
Number

Output Ratings

Input Ratings

Branch Circuit Protection

kW (HP)

Amps

Voltage
Range

kVA Amps Fuses

140M Motor
Protectors

(2)

(3)

Contactors

Min. Enclosure
Volume

(4)

(in.

3

)

100 - 120V AC (±10%) – 1-Phase Input, 0 - 230V 3-Phase Output

22A-V1P5N104

0.2 (0.25) 1.5

90-126

0.75 6.0

10

140M-C2E-C10

100-C09

1655

22A-V2P3N104

0.4 (0.5)

2.3

90-126

1.15 9.0

15

140M-C2E-C16

100-C12

1655

22A-V4P5N104

0.75 (1.0) 4.5

90-126

2.25 18.0

30

140M-D8E-C20

100-C23

1655

22A-V6P0N104

1.1 (1.5)

6.0

90-126

3.0

24.0

40

140M-F8E-C32

100-C37

1655

200 - 240V AC (±10%) – 1-Phase

(1)

Input, 0 - 230V 3-Phase Output, NO BRAKE

22A-A1P4N103

0.2 (0.25) 1.4

180-265 0.7

3.2

6

140M-C2E-B40

100-C09

1655

22A-A2P1N103

0.4 (0.5)

2.1

180-265 1.05 5.3

10

140M-C2E-B63

100-C09

1655

22A-A3P6N103

0.75 (1.0) 3.6

180-265 1.8

9.2

15

140M-C2E-C16

100-C12

1655

22A-A6P8N103

1.5 (2.0)

6.8

180-265 3.4

14.2

25

140M-C2E-C16

100-C16

1655

22A-A9P6N103

2.2 (3.0)

9.6

180-265 4.8

19.6

30

140M-D8E-C25

100-C23

1655

200 - 240V AC (±10%) – 1-Phase

(1)

Input, 0 - 230V 3-Phase Output

22A-A1P5N104

0.2 (0.25) 1.5

180-265 0.75 5.0

10

140M-C2E-B63

100-C09

1655

22A-A2P3N104

0.4 (0.5)

2.3

180-265 1.15 6.0

10

140M-C2E-B63

100-C09

1655

22A-A4P5N104

0.75 (1.0) 4.5

180-265 2.25 10.0

15

140M-C2E-C16

100-C12

1655

22A-A8P0N104

1.5 (2.0)

8.0

180-265 4.0

18.0

30

140M-D8E-C20

100-C23

1655

200 - 240V AC (±10%) – 3-Phase Input, 0 - 230V 3-Phase Output

22A-B1P5N104

0.2 (0.25) 1.5

180-265 0.75 1.8

3

140M-C2E-B25

100-C09

1655

22A-B2P3N104

0.4 (0.5)

2.3

180-265 1.15 2.5

6

140M-C2E-B40

100-C09

1655

22A-B4P5N104

0.75 (1.0) 4.5

180-265 2.25 5.2

10

140M-C2E-C10

100-C09

1655

22A-B8P0N104

1.5 (2.0)

8.0

180-265 4.0

9.5

15

140M-C2E-C16

100-C12

1655

22A-B012N104

2.2 (3.0)

12.0

180-265 5.5

15.5

25

140M-C2E-C16

100-C16

1655

22A-B017N104

3.7 (5.0)

17.5

180-265 8.6

21.0

30

140M-F8E-C25

100-C23

1655

380 - 480V AC (±10%) – 3-Phase

Input, 0 - 460V 3-Phase Output

22A-D1P4N104 0.4 (0.5)

1.4

340-528 1.4

1.8

3

140M-C2E-B25

100-C09

1655

22A-D2P3N104 0.75 (1.0) 2.3

340-528 2.3

3.2

6

140M-C2E-B40

100-C09

1655

22A-D4P0N104 1.5 (2.0)

4.0

340-528 4.0

5.7

10

140M-C2E-B63

100-C09

1655

22A-D6P0N104 2.2 (3.0)

6.0

340-528 5.9

7.5

15

140M-C2E-C10

100-C09

1655

22A-D8P7N104 3.7 (5.0)

8.7

340-528 8.6

9.0

15

140M-C2E-C16

100-C16

1655

Input/Output Ratings

Approvals

Output Frequency: 0-240 Hz (Programmable)

Efficiency: 97.5% (Typical)

Digital Control Inputs (Input Current = 6mA)

Analog Control Inputs

SRC (Source) Mode:

18-24V = ON
0-6V = OFF

SNK (Sink) Mode:

0-6V = ON
18-24V = OFF

4-20mA Analog: 250 ohm input impedance
0-10V DC Analog: 100k ohm input impedance
External Pot: 1-10k ohms, 2 Watt minimum

Control Output (Programmable Output, form C relay)

Resistive Rating: 3.0A at 30V DC, 125V AC and 240V AC

Inductive Rating: 0.5A at 30V DC, 125V AC, and 240V AC

Recommended Fuses and Circuit Breakers

Fuse: UL Class J, CC, T or Type BS88; 600V (550V) or equivalent. Circuit Breakers: HMCP or Bulletin 140U or equivalent.

Protective Features

Motor Protection: I

2

t overload protection - 150% for 60 Secs, 200% for 3 Secs (Provides Class 10 protection)

Overcurrent: 200% hardware limit, 300% instantaneous fault
Over Voltage:

100-120V AC Input – Trip occurs at 405V DC bus voltage (equivalent to 150V AC incoming line)
200-240V AC Input – Trip occurs at 405V DC bus voltage (equivalent to 290V AC incoming line)
380-460V AC Input – Trip occurs at 810V DC bus voltage (equivalent to 575V AC incoming line)

Under Voltage:

100-120V AC Input – Trip occurs at 210V DC bus voltage (equivalent to 75V AC incoming line)
200-240V AC Input – Trip occurs at 210V DC bus voltage (equivalent to 150V AC incoming line)
380-480V AC Input – Trip occurs at 390V DC bus voltage (equivalent to 275V AC incoming line)

Control Ride Through: Minimum ride through is 0.5 Secs - typical value 2 Secs
Faultless Power Ride Through: 100 milliseconds

Dynamic Braking

Internal brake IGBT included with all ratings except No Brake versions. Refer to Appendix B of the PowerFlex 4 User Manual
on CD for ordering information.

(1)

200-240V AC - 1-Phase drives are also available with an integral EMC filter. Catalog suffix changes from N103 to N113

and N104 to N114.

(2)

The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See

Bulletin 140M Motor Protection

Circuit Breakers Application Ratings

.

UL

®

UL508C
CSA 22.2
No. 14

C

US

EMC Directive 89/336/EEC, LV Dir. 73/23/EEC
LV: EN

50178

EMC:

EN

61800-3