Advanced Program Group

(continued)

A056 [Relay Out Level]

Related Parameter(s):

A055

32 bit parameter.

Sets the trip point for the digital output relay if the value of

A055

[Relay Out Sel] is 6, 7, 8, 10 or 20.

Values

Default

0.0

Min/Max:

0.0/9999

Display:

0.1

32

A055 Setting

A056 Min/Max

6
7
8
10
20

0/240 Hz
0/180%
0/815 Volts
0/100%
0/1

A067 [Accel Time 2]

Related Parameter(s):

P039

When active, sets the rate of acceleration for all speed increases except jog. Refer to the flowchart on

page 1-19

for details.

Values

Default

20.0 Secs

Min/Max:

0.0/600.0 Secs

Display:

0.1 Secs

Maximum Freq

Accel Time

Accel Rate

=

Speed

0

Time

P035 [Maximum Freq]

P039 or A067

[Accel Time x]

P040 or A068

[Decel Time x]

0

Acceleration

D

eceleration

A068 [Decel Time 2]

Related Parameter(s):

P040

When active, sets the rate of deceleration for all speed decreases except jog. Refer to the flowchart
on

page 1-19

for details.

Values

Default

20.0 Secs

Min/Max:

0.1/600.0 Secs

Display:

0.1 Secs