Page 22

background image

1-12

Installation/Wiring

Control Wire Types

Table 1.G Recommended Control and Signal Wire

(1)

I/O Terminal Block

Table 1.H I/O Terminal Block Specifications

Maximum Control Wire Recommendations

Do not exceed control wiring length of 30 meters (100 feet). Control
signal cable length is highly dependent on electrical environment and
installation practices. To improve noise immunity, the I/O terminal
block Common must be connected to ground terminal/protective earth.
If using the RS485 (DSI) port, I/O Terminal 16 should also be connected
to ground terminal/protective earth.

Wire Type(s)

Description

Minimum
Insulation Rating

Belden 8760/9460
(or equiv.)

0.8 mm

2

(18AWG), twisted pair, 100%

shield with drain.

(1)

(1)

If the wires are short and contained within a cabinet which has no sensitive circuits,
the use of shielded wire may not be necessary, but is always recommended.

300V
60 degrees C
(140 degrees F)

Belden 8770
(or equiv.)

0.8 mm

2

(18AWG), 3 conductor, shielded for

remote pot only.

Maximum Wire Size

(1)

(1)

Maximum/minimum sizes that the terminal block will accept - these are not
recommendations.

Minimum Wire Size

(1)

Torque

1.3 mm

2

(16 AWG)

0.13 mm

2

(26 AWG)

0.5-0.8 N-m (4.4-7 lb.-in.)