Rockwell Automation 22A PowerFlex 4 User Manual FRN 6.xx User Manual
Page 70
4-6
Troubleshooting
Drive does not Start from Start or Run Inputs wired to the terminal block.
Drive does not respond to changes in speed command.
Cause(s)
Indication
Corrective Action
Drive is Faulted
Flashing red status light
Clear fault.
•
Press Stop
•
Cycle power
•
to option 1
“Clear Faults”.
•
Cycle digital input if
[Digital Inx Select] is set to option
7 “Clear Fault”.
Incorrect programming.
•
[Start Source] is set to
option 0 “Keypad” or option 5
“RS485 (DSI) Port”.
•
[Digital Inx Select]
is set to option 5 “Local” and the
input is active.
None
Check parameter settings.
Incorrect input wiring.
See
for wiring examples.
•
2 wire control requires Run
Forward, Run Reverse or Jog
input.
•
3 wire control requires Start and
Stop inputs
•
Stop input is always required.
None
Wire inputs correctly and/or install
jumper.
Incorrect Sink/Source DIP switch
setting.
None
Set switch to match wiring scheme.
Cause(s)
Indication
Corrective Action
No value is coming from the
source of the command.
The drive “Run” indicator is lit
and output is 0 Hz.
•
Check d012
[Control
Source] for correct source.
•
If the source is an analog input,
check wiring and use a meter to
check for presence of signal.
•
Check
[Commanded Freq]
to verify correct command.
Incorrect reference source is
being selected via remote
device or digital inputs.
None
•
Check
[Control Source] for
correct source.
•
Check
[Dig In Status] to
see if inputs are selecting an
alternate source. Verify settings
for
[Digital Inx
Select].
•
Check
[Speed Reference]
for the source of the speed
reference. Reprogram as
necessary.
•
Review the Speed Reference
Control chart on
.