A080, A081, A079 – Rockwell Automation 22A PowerFlex 4 User Manual FRN 6.xx User Manual
Page 53: Advanced program group, Continued), A079 [jog accel/decel, A080 [dc brake time, A081 [dc brake level, Programming and parameters 3-17
Programming and Parameters
3-17
Advanced Program Group
(continued)
A079 [Jog Accel/Decel]
Related Parameter(s):
,
Sets the acceleration and deceleration time when a jog command is issued.
Values
Default
10.0 Secs
Min/Max:
0.1/600.0 Secs
Display:
0.1 Secs
A080 [DC Brake Time]
Related Parameter(s):
Sets the length of time that DC brake current is “injected” into the motor. Refer to parameter
[DC
Brake Level].
Values
Default
0.0 Secs
Min/Max:
0.0/90.0 Secs
Display:
0.1 Secs
A081 [DC Brake Level]
Related Parameter(s):
Defines the maximum DC brake current, in amps, applied to the motor when
[Stop Mode] is set
to either “Ramp” or “DC Brake”.
Values
Default
Drive Rated Amps
×
0.05
Min/Max:
0.0/(Drive Rated Amps
×
1.8)
Display:
0.1 Amps
DC Injection Braking Mode
V
olts/S
p
eed
Voltage
Time
Stop Command
Speed
[DC Brake Level]
[DC Brake Time]
V
olts/S
p
eed
Ramp-to-Stop Mode
Time
Stop Command
[DC Brake Level]
[DC Brake Time]
Voltage
Speed
!
ATTENTION:
If a hazard of injury due to movement of equipment or material exists,
an auxiliary mechanical braking device must be used.
!
ATTENTION:
This feature should not be used with synchronous or permanent
magnet motors. Motors may be demagnetized during braking.