Sdc models, De / 101-kde, Remote rex remote reset – SDC 101-DE/101-KDE Delayed Egress Controller User Manual
Page 6: Dip switch settings, Jumper j1
MODEL 101-DE
MODEL 101-KDE
P:\INSTALLATION INST\Delayed Egress\INST-101DE_KDE.vsd Rev B10 04-13 Page 6
CONTROLLER SPECIFICATIONS
INPUT VOLTAGE
12 VDC OR 24 VDC
MAX CURRENT DRAW 180mA @ 12/24 VDC
(CONTROLLER ONLY)
MAX CURRENT
1 Amp @ 12/24 VDC
(LOCK OUTPUT)
MONITOR RELAYS
1 Amp @ 12/24 VDC
CONTACT RATING (RESISTIVE)
TEMPERATURE
0 C – 70 C
o
o
*JUMPER J1 (DOOR PROP)
INSTALLED: The 101DE/KDE will enter the alarm mode if the
door is held open past the request to exit period.
REMOVED: The 101DE/KDE will remain unlocked if the door is
held open past the request to exit period. No alarm will sound.
The 101DE/KDE will relock and rearm upon closure of the door.
Note for 1581DE only:
Peel double sided tape on
trigger switch clip and stick
flush against end-block and
sidewall as shown.
Trigger
Switch
-
+
345
67
8
SDC MODELS
To
Power
Supply
1511DE 1575DE
1571DE 1576DE
1581DE
101-DE / 101-KDE
PWR LOCKRED ONLY
TRIG REX
RESET
C NO
C NO
C NO
- +
- +
GRN ONLY
REMOTE
REX
REMOTE
RESET
Trigger
Switch
Trigger
Switch
-
+
345
678
-
+
345
678
l
PAIR OF
DOORS
101-DE
101-KDE
PWR LOCK RED R
NO C
TRIG REX RESET
C NO
C NO
C NO
- +
- +
To
Power
Supply
WARNING!
CONTACT THE AUTHORITY HAVING JURISDICTION FOR APPROVAL
PRIOR TO SELECTING DELAY TIME OR PWR-UP SETTINGS
Functionality of the switches vary with the program option code. See Page 2
for a detailed description.
*
DIP SWITCH
SETTINGS
15
30
1
2
15
20
30
1
N/C
N/O
UNLOCKED
LOCKED
VOICE/TONE
TONE
ONLY
FEMALE
MSG
MALE
MSG
ON
DELAY
TIME
[ON]
[OFF]
1
23
4
5
6
7
8
NUISANCE
DELAY
REX/BYPASS
PERIOD
TRIGGER
TYPE
PWR UP
STATE
ALARM
TYPE
MESSAGE
JUMPER J1*
*
*
*
NO C NC
NO C NC