beautypg.com

SDC 920P EntryCheck User Manual

Page 6

background image

Beep Sounds During Auxiliary Relay

Default: No

Selects whether or not the keypad beeps during Auxiliary Relay
activation.

Press: 42 # Sound #

Sound=1 for Yes, =0 for No

Beep Sounds During Output #3

Default: No

Selects whether or not the keypad beeps during Output #3
activation.

Press: 43 # Sound #

Sound=1 for Yes, =0 for No

Beep Sounds During Output #4

Default: No

Selects whether or not the keypad beeps during Output #4
activation.

Press: 44 # Sound #

Sound=1 for Yes, =0 for No

Anti-Pass Back Time

Default: No Anti-Pass Back

Sets the length of time an entry code will not function after it is
used.

Press: 51 # Minutes #

Minutes=Time in minutes (2-4), 0=No Anti-passback

RESETTING KEYPAD

Master Reset

CAUTION: Performing a master reset will clear the
entire memory of the 920P and return all programmable
options to the factory default values. ALL ENTRY
CODES WILL BE ERASED. NOTE: The Master Code will
NOT be reset.

STEP 1 Disconnect power from the keypad.
STEP 2 Press and hold down the * and # keys.
STEP 3 Apply power to the keypad, continue holding the keys

down until the red indicator starts flashing

STEP 4 Release the keys. The red and yellow indicators will

remain lit until the process is complete, then the
yellow indicator will go out.

Resetting the Master Code

STEP 1 Remove the 920P from the wall and disconnect

power from the keypad.

STEP 2 Locate & Remove jumper at JP2. Reference page 2.
STEP 3 Re-apply power. You will get a single beep and

the yellow LED will flash momentarily.

STEP 4 Replace jumper on JP2.

THE MASTER PROGRAMMING CODE IS NOW 123456.

Beep Sounds During Main Relay

Default: No

Selects whether or not the keypad beeps during Main Relay
activation.

Press: 41 # Sound #

Sound=1 for Yes, =0 for No

Solid-state Output #4 On-time

Default: 02 Seconds

Sets the length of time Output #4 activates when triggered.

Press: 24 # Seconds #

Seconds=Output time in seconds (1-60), 99=Toggle Mode

Beep Sounds on Keystrokes

Default: Yes

Selects whether or not the keypad beeps as each key is pressed.

Press: 40 # Sound #

Sound=1 for Yes, =0 for No

P:\INSTALLATION INST\Access Controls\INST-920\INST-920P.vsd Rev D 03-14 Page 6

Selects mode for Keypad LED Backlight

Default: 30 Seconds

Selects whether or not the keypad back light stays OFF, lights for 30
seconds when activated or stays ON.

Press: 52 # Output #

0 = Light always OFF

1 = 30 sec light when activated (default)

2 = Light always ON

Solid-state Output #3 On-time

Default: 02 Seconds

Sets the length of time Output #3 activates when triggered.

Press: 23 # Seconds #

Seconds=Output time in seconds (1-60), 99=Toggle Mode

Beep Sounds Anti-Tamper Activation

Default: No

Selects whether or not the keypad beeps during Anti-Tamper
switch activation.

Press: 45 # Sound #

Sound=1 for Yes, =0 for No

Changing the Beeper Sound Level

The Keypad’s beeper can be set to high or low level.
Remove jumper JP1 to reduce beeper sound level.

Changing the 6-Digit Master Programming Code

Press: 98 # Master Code # Master Code #

Master Code=The new 6-digit Master Programming Code

Keypad Lockout Count

Default: 3 Attempts

Sets the number or incorrect entry code attempts allowed
before the keypad “locks out” for 60 seconds.

Press: 50 # Attempts #

Attempts=Number of attempts before lockout (2-7)

*Refer to Option 13 to Enable Lockout Feature

Door Ajar Timer

Default: 60 Seconds

Sets the amount of time the door may be held open after an
authorized access. The DOOR AJAR output will activate after the
time expires.

Press: 25 # Seconds #

Seconds=Output time in seconds (1-60), 99=Toggle Mode