KEYPAD WIRING

See Fig. 3 for an example of a basic door installation. The keypad is
mounted adjacent to the door. An electric door strike is mounted in the
door jamb to release the door lock. A magnetic switch is mounted on top
of the door jamb for detecting when the door is open.

Use the following steps to wire the keypad. Refer to the wiring diagram
shown in Fig. 4 to assist in the wiring.

Note: Up to 500 feet of 18 AWG wire can be run for power, use larger wire
for longer runs. Use 22 AWG or larger (depending on load) for other
connections. Refer to lock manufacturer’s documentation for
recommended lock power AWG.

Output Connection

Install a low voltage fail secure (power to unlock) electric door strike at the
door to be controlled. Route two wires from the door strike to the keypad.
Connect a MOV or varistor across the coil wires of the strike. Connect the
(+) door strike wire to the keypad’s MAIN RELAY N.O wire (yellow).
Connect the other door strike wire to the keypad’s PWR(-) wire (black).
Connect the keypad’s MAIN RELAY COM wire (white), to the keypad’s
PWR(+) wire (red) .

Power Connection

Choose a location for the DC power supply or AC transformer.
Route two wires between the door strike and the keypad . Connect the
power supply’s output terminals to the keypad’s PWR(+) wire (red) and
PWR(-) wire (black). If using a DC supply, Observe wiring polarity. If an
AC transformer is being used, polarity does not mater.

Caution: If the unit is AC powered, make sure the secondary of
the system transformer is isolated from earth ground.

Earth Ground

To avoid damage to the unit from static discharges, connect the earth
ground wire (green/E5) to a good earth grounding point. Suggested
wiring size is 18 AWG for earth ground.

Sense Input

RE

Note: The SENSE input (gray wire) can be programmed as either a

door sense or inhibit input. Both features cannot be used at the same
time. If you are not using the sense input, program this input for inhibit.

Door Sense: (Detect forced entry or door ajar conditions) Install a
normally closed door switch on the door and route two wires from the
switch to the keypad. Connect the door switch to the keypad’s SENSE
wire (gray/ E8) and COM wire (any black wire).

Inhibit: (Disable access) If an inhibit switch or timer is going to be used for
temporarily disabling the keypad, route two wires from the switch or timer
to the keypad. Connect the inhibit switch/timer’s normally open contacts
to the keypad’s SENSE (gray/ E8) and COM (black wires) terminal.

Request-to-Exit Input

(wiring shown on page 3, fig. 4)

If a request-to-exit pushbutton is going to be used, route two wires from
the keypad box to a normally open pushbutton mounted on the secure
side of the door. Connect the wires to the pushbutton and to the keypad’s
REX wire (violet/ E6) and COM (black wires) terminals.

Solid State Outputs

The two solid state outputs (Outputs #3 & #4) can be programmed to
activate during various conditions. These “open collector” outputs can be
used to activate indicators or sounders. See fig. 5 for wiring examples
using the solid state outputs.

P:\INSTALLATION INST\Access Controls\INST-920\INST-920P.vsd Rev D 03-14 Page 3

Fig. 5 Using Solid State Outputs

Fig. 3 Basic Door Installation

OUTPUT #3 LIGHTS AN LED
OUTPUT #4 LIGHTS AN LED AND SOUNDS A BEEPER

EXAMPLE #1:

POWER
SUPPLY

+

LED

LED

BLUE

PINK/SALMON

1KΩ

1KΩ

-

+

OUTPUT #3

OUTPUT #4

ELECTRONIC

BEEPER

OUTPUT #3 LIGHTS A LAMP POWERED FROM AN EXTERNAL SOURCE
OUTPUT #4 TRIGGERS A NORMALLY OPEN ALARM PANEL ZONE

EXAMPLE #2:

BLUE

PINK/SALMON

OUTPUT #3 COM

OUTPUT #4 COM

POWER

SOURCE

OUTPUT #3

END OF LINE

RESISTOR

ALARM PANEL

NO ZONE

COMMON

LOW

VOLTAGE

LAMP

-

+

BLACK

BLACK

OUTPUT #4

EACH

OUTPUT

100 mA

MAXIMUM

W

ir

e

P

ig

ta

il

W

ir

e

P

ig

ta

il

920P

Keypad

Fig. 4 Basic Door Installation Wiring

TO POWER SUPPLY

KEY PAD POWER

12-24 VOLTS

AC OR DC

}

+

-

RED

BLACK

AUXILIARY RELAY

2 AMPS @ 28VDC

MAX

}

NC

NO

COM

ORG/BLK

BLK/WHT

BRN/YEL

FAIL SECURE CONNECTION

FAIL SAFE CONNECTION

MAIN RELAY

5 AMPS @ 28VDC

MAX

}

NC

COM

NO

ORANGE

WHITE

YELLOW

BLACK

PINK/SALMON

GREEN

GRAY

BLACK

VIOLET

BLACK

BLUE

DOOR POSITION

SWITCH

[N/C]

REQUEST-TO-EXIT

SWITCH

[N/O]

COMMON

OUTPUT #4

OUTPUT #3

EARTH GROUND

COMMON

SENSE

REQUEST TO EXIT

COMMON

EARTH

GROUND

CONNECTION

WIRE PIGTAIL

E

1

E

8

E

7

E

6

E

5

E

4

E

3

E

2

C

NO

C

NC

NO

AUXILIARY OUTPUTS

100mA MAX TO COMMON

{

*

*