‎Chapter 1 General Information

BFM136 Branch Feeder Monitor

7

Chapter 1 General Information

The BFM136 is a 3-phase, multi-channel, multi-function energy meter
suitable for use in single-phase and multi-phase electrical networks.

Meter highlights

Multi-channel submetering – up to 36 single-phase or 18 two-phase

or 12 three-phase submeters in a single device. Any combination of
single-, two-, and three-phase consumers can be chosen up to a
total of 36 current inputs.

Automatic totalization energy from different sub-consumers

Features

Calibrated to meet Class 0.5S active energy and Class 1 reactive

energy meter accuracy

3-phase/2-phase/single-phase meters (true RMS, volts, amps,

power, power factor, neutral current)

Ampere/Volt demand meter

Time-of-Use, 4 energy/demand registers x 6 tariffs

1

, 4 seasons x 4

types of days, 8 tariff changes per day, easy programmable tariff
schedule

Import/export energy and power demands

Automatic 120–day daily profile for import/export

2

energy and

maximum demand readings (total and tariff registers) separate for
each submeter

Event recorder for logging internal diagnostic events and setpoint

operations

Data recorders; programmable periodical data logs separate for

each submeter

Embedded programmable controller (4 control setpoints,

programmable thresholds and delays) separate for each submeter

Easy to read 2-row x 16 characters LCD display with backlight

(BFM136 only)

50/60 Hz operation

Internal clock, keeping the clock running over one week without

external power

HACS with overvoltage protection diodes to avoid any damage

while disconnecting the primary current sensor

Standard RS-485 serial port

Optional second communication port. Communication options
available:

RS-232
RS-422/485
56K Dial-up modem
Ethernet 10/100BaseT
Wireless RF modem (unlicensed 907-922 MHz)

Modbus RTU and Modbus ASCII communication protocols

Easy field upgrading device firmware through any communication

port

1

From Firmware version 18.4.1

2

From Firmware version 18.5.1