Device options, Communication ports – SATEC BFM136 User Manual
Page 32
Chapter 3 BFM136 Display Operations
Menu Operations
32
BFM136 Branch Feeder Monitor
Label
Parameter
Options
Default
Description
Ratio V1-V3
V1-V3 voltage
transformer
ratio correction
factor
0.700 to 1.300
1.000
The ratio of the true
transformer ratio to the
marked ratio.
Angle V1-V3
V1-V3
transformer
phase angle
error, minutes
-600 to 600
0
The phase
displacement, in
minutes, between the
primary and secondary
values. The phase
angle of a voltage
transformer is positive
when the secondary
value leads the primary
value.
Ratio I1-I36
I1-I36 current
transformer
ratio correction
factor
0.700 to 1.300
1.000
The ratio of the true
transformer ratio to the
marked ratio.
Angle I1-I36
I1-I36
transformer
phase angle
error, minutes
-600 to 600
0
The phase
displacement, in
minutes, between the
primary and secondary
values. The phase
angle of a current
transformer is positive
when the secondary
value leads the primary
value.
Device Options
This menu allows you to select some user-configurable device options or put
the BFM136 into energy test mode.
To enter the menu, select the Options entry from the main menu, then press
ENTER. For instructions on navigating in the menu, see
The following table lists available options.
Label
Parameter
Options
Default
Description
PowMode
Power
calculation
mode
Reactive,
NonActive (non-
active power)
Reactive
The method used for
calculating reactive
and apparent powers
ErgyRoll
Energy roll
value
100000.0-
100000000.0
kWh
100000000.0 The value at which
energy counters roll
over to zero
TestMode
Energy test
mode
OFF, Wh, varh OFF
Setting this option
puts the device into
the energy test mode
PlsConst
Wh LED pulse
rate,
Wh/pulse
0.01-100.00
5.40Wh/pulse
(one
equivalent
disk
revolution)
LED pulse constant -
the amount of
accumulated energy
giving one pulse via
“Wh” LED
WhLEDSrc Energy LED
source
1-40, None
1
Selects a submeter as
a LED pulsing source
Communication Ports
These two menus allow you to configure parameters for communication
ports COM1 and COM2. The BFM136 automatically detects a replaceable
communication module and will not allow you to change the baud rate and
data format for the Dial-up modem, and for the Ethernet and RF modules.
Options
Exit
Options PowMode
Reactive
ENTER