Local network settings, Local settings – SATEC BFM136 User Manual
Page 33
Chapter 3 BFM136 Display Operations
Menu Operations
BFM136 Branch Feeder Monitor
33
To enter the menu, select the COM1 or COM2 entry from the main menu,
and then press the ENTER button. For instructions on navigating in the
menu, see
Viewing and Changing Setup Items
The following table lists available port options.
Label
Parameter
Options
Default
Description
Protocol
Communication
s protocol
Modbus RTU,
Modbus ASCII
Modbus
RTU
The communications
protocol for the port
Interface
Port interface
RS485
RS485, RS232,
Modem,
Ethernet, RF
COM1
COM2
Not changeable;
automatically detected
by the device
Address
Device address 1-247
1
Device’s base network
address (see
Baud rate
Baud rate
2.4-115.2 kbps 19.2 kbps
The port baud rate
Data/Prty
Data format and
parity
7E, 8N, 8E
8N
7E data format should
not be used with the
Modbus RTU protocol
Send Delay Transmission
delay
0-1000 ms
5 ms
The minimum time after
the last request
character is received to
start the transmission.
Chr.Tmout
Inter-character
timeout
0-1000 ms
4 ms
The maximum time the
line is allowed to idle
before closing a
connection in the
Modbus RTU protocol
NOTE
When using the ExpertPower
client (see
Configuring eXpertPower Client
submeter address 99 on the Ethernet port COM2 is reserved for the BFM136
router and must not fall inside the range of the submeter addresses for this
port.
Local Network Settings
This menu allows you to configure the Ethernet modem (if present) for direct
communications through the LAN or the Internet.
To enter the menu, select the Net entry from the main menu, and then press
the ENTER button. For instructions on navigating in the menu, see
The following table lists available Ethernet options.
Label
Default
Description
IP Address
192.168.0.203
Device IP address
Subnet Mask
255.255.255.0
Subnet mask
Def.Gateway
192.168.0.1
Default gateway
Local Settings
This menu allows you to configure your local time zone settings.
To enter the menu, select the Local entry from the main menu, and then
press the ENTER button. For instructions on navigating in the menu, see
Viewing and Changing Setup Items
The following table lists available options.
COM1
Exit
COM1
Protocol
Modbus RTU
ENTER
Net Exit
Net IP Address
192.168.000.203
ENTER
Local Exit
Local Country
Default
ENTER