Appendix e data scales – SATEC BFM136 User Manual
Page 69
Appendix E Data Scales
BFM136 Branch Feeder Monitor
69
Appendix E
Data Scales
The maximum values for volts, amps and power in the BFM136 setup and in
communications are limited by the voltage and current scale settings. See
in Chapter 4 on how to change the voltage scale in your
meter.
The following table defines the meter data scales.
Scale
Range
Notes
Maximum voltage (V max) Voltage scale
PT Ratio, V
The default voltage
scale is 600V
Maximum current (I max)
HACS Primary current
2, A
The default HACS
primary current is
50A
Maximum power
1
V max
I max
2, W
1
Maximum power is rounded to whole kilowatts. With PT=1.0, it is limited
to 9,999,000 W.