Local settings – SATEC BFM136 User Manual
Page 46
![background image](/manuals/572118/46/background.png)
Chapter 4 PAS Application Software
General Meter Setup
46
BFM136 Branch Feeder Monitor
The following table lists available options.
Parameter
Options
Default
Description
Ratio Correction
Factor
0.700 to 1.300
1.000
The ratio of the true transformer
ratio to the marked ratio.
Phase Angle Error,
minutes
-600 to 600
0
The phase displacement, in
minutes, between the primary
and secondary values. The
phase angle of a transformer is
positive when the secondary
value leads the primary value.
Local Settings
The Local Settings setup allows you to specify your time zone and daylight
saving time options.
To configure the time zone options for your device, select the device site
from the list box on the PAS toolbar, select General Setup from the Meter
Setup menu, and then click on the Local Settings tab.