C13861 | 0x1f8c nmt communication status, C13864 | 0x1f93.1 node id, C13865 | 0x1f93.2 node id by hw – Lenze E84AYCEC User Manual
Page 76: C13861, And the red, E84aycec communication manual (ethernet powerlink)

E84AYCEC communication manual (Ethernet POWERLINK)
Parameter reference
Parameters of the communication module
76
L
EDS84AYCEC EN 3.0 - 09/2012
C13861
C13864
C13865
Parameter | Name:
C13861 | 0x1F8C NMT Communication Status
Data type: UNSIGNED_8
Index: 10714
d
= 29DA
h
The code displays the current NMT state (according to the Ethernet POWERLINK specification) of the EPL node.
Selection list
(read only)
Info
0 Off
NMT_GS_OFF
25 Initialising
NMT_GS_INITIALISING
41 ResetAppl
NMT_GS_RESET_APPLICATION
57 ResetComm
NMT_GS_RESET_CONFIGURATION
121 ResetConfig
NMT_GS_RESET_CONFIGURATION
28 NotActive
NMT_CS_NOT_ACTIVE
29 PreOp1
NMT_CS_PRE_OPERATIONAL_2
93 PreOp2
NMT_CS_PRE_OPERATIONAL_2
109 ReadyToOp
NMT_CS_READY_TO_OPERATE
253 Operational
NMT_CS_OPERATIONAL
77 Stopped
NMT_CS_STOPPED
30 BasicEthernet
NMT_CS_BASIC_ETHERNET
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13864 | 0x1F93.1 Node ID
Data type: UNSIGNED_8
Index: 10711
d
= 29D7
h
The code displays the currently valid EPL node address (Node ID).
• The node ID must be unequivocal in the EPL network segment.
Display range
(min. value | unit | max. value)
1
239
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13865 | 0x1F93.2 Node ID by HW
Data type: UNSIGNED_8
Index: 10710
d
= 29D6
h
The code indicates whether the EPL node address (node ID) has been set via rotary encoder switches at the
communication module or via the software.
• 0 (FALSE): Node ID has been set via software (
).
• 1 (TRUE): node ID has been set via rotary encoder switches at the communication module.
Display range
(min. value | unit | max. value)
0
1
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT