Set station configuration, Function selector switch, Station installation – ETC Echo Inspire Station User Manual
Page 3: Page 3 of 8 inspire station installation guide, Front of station rear of station

E T C I n s t a l l a t i o n G u i d e
Station Installation
Page 3 of 8
Inspire Station Installation Guide
b: Use one WAGO connector, provided in the termination kit, to connect
the power pigtail and the installed control wires.
Open the terminal
levers on the WAGO connector and insert the installed (typically
black) Belden 8471 wire and the black lead from the power pigtail
into the terminals. Then close the levers.
c: Repeat for the installed (typically white) Belden 8471 power wires and
the remaining white wire from the power pigtail using a new WAGO
connector.
d: Install the two pin connector from the power pigtail to the mating
receptacle on the station electronics.
Set Station Configuration
Inspire stations have on-board switch and mode button settings that determine
functionality, space assignment, and station address.
Function Selector Switch
Sets the station functionality to PRESET, CUSTOM, or ZONE. The Program
Mode switch setting also affects the function of this Function Switch.
•
PRESET - When set, all buttons on the station will perform preset
related actions. Preset functionality is the default.
•
CUSTOM - This function is reserved for future development.
•
ZONE- When set, all buttons on the station will perform zone related
actions; allowing manual adjustment of zone levels to record (snapshot)
presets for later recall.
24VDC, @5mA
For use with Unison Echo and
Sensor3 Control Systems Only.
Type 1
LISTED
IND. CONTROL EQUIP
9Z49
ENERGY MGMT. EQUIP
Switches
1 - Use Off
2 - Amber LED Disable
8 - Restore Defaults
RECORD/
PROGRAM
MODE
Function switch
PRESET
CUSTOM
ZONE
front of
station
rear of
station