Unison Paradigm BACnet Interface Object Reference Guide

1.3 Binary Input Object Type

Binary Input: BACnet Properties List

Is the Object Type Proprietary?

No, compliant with Clause 12.6 of the ASHRAE Standard BACnet 135-2004 document.

Does the Object Type contain any Proprietary Properties?

Yes, the "Binary_BCID" property.

General Description of Object Type

Binary Input objects are only created by the Paradigm Central Control Server (P-CCS)

based on the LightDesigner configuration and may be used to provide general user-defined

binary or switched feedback for objects within a Paradigm system.

Each object instance for this "Object_Type" has an "Object_Identifier" that is unique for this

type and "Object_Name".

The BACnet object instance is managed by the P-CCS, based on the configuration using

Paradigm LightDesigner software. An "Binary Input" object is created for each "Indicator"

object with functional assignment on the BACnet I/O panel within LightDesigner, up to a

maximum of 1000 objects.

The "Present_Value" property will always have the objects Boolean

("ACTIVE" / "INACTIVE") value. The "Present_Value" is read-only and is not changeable

by the BACnet client. The "Binary_Input_BCID", (EtcBACnetCID) property will be provided

a value that is unique within the storage of the BACnet interface device and the P-CCS sub-

system.

Property Identifier

Property Datatype

Property Brief Description

Object_Identifier

BACnetObjectIdentifier

Numeric code uniquely identifying this object

Object_Name

CharacterString

Alphanumeric string identifying this object

Object_Type

BACnetObjectType

Always: "BINARY_INPUT"

Present_Value

BACnetBinaryPV

Current value of this object: "ACTIVE" / "INACTIVE"

Description

CharacterString

Alphanumeric description of this object

Status_Flags

BACnetStatusFlags

Always: "{false, false, false, false}"

Event_State BACnetEventState

Always:

"NORMAL"

Out_Of_Service

BOOLEAN

Always: "false"

Binary_Input_BCID EtcBACnetCID

Unique

16

byte identifier assigned by P-CCS