3 binary input object type, Binary input: bacnet properties list, General description of object type – ETC Unison Paradigm Central Control Server BACnet Interface Reference Guide User Manual
Page 8
4
Unison Paradigm BACnet Interface Object Reference Guide
1.3 Binary Input Object Type
Binary Input: BACnet Properties List
Is the Object Type Proprietary?
No, compliant with Clause 12.6 of the ASHRAE Standard BACnet 135-2004 document.
Does the Object Type contain any Proprietary Properties?
Yes, the "Binary_BCID" property.
General Description of Object Type
Binary Input objects are only created by the Paradigm Central Control Server (P-CCS)
based on the LightDesigner configuration and may be used to provide general user-defined
binary or switched feedback for objects within a Paradigm system.
Each object instance for this "Object_Type" has an "Object_Identifier" that is unique for this
type and "Object_Name".
The BACnet object instance is managed by the P-CCS, based on the configuration using
Paradigm LightDesigner software. An "Binary Input" object is created for each "Indicator"
object with functional assignment on the BACnet I/O panel within LightDesigner, up to a
maximum of 1000 objects.
The "Present_Value" property will always have the objects Boolean
("ACTIVE" / "INACTIVE") value. The "Present_Value" is read-only and is not changeable
by the BACnet client. The "Binary_Input_BCID", (EtcBACnetCID) property will be provided
a value that is unique within the storage of the BACnet interface device and the P-CCS sub-
system.
Property Identifier
Property Datatype
Property Brief Description
Object_Identifier
BACnetObjectIdentifier
Numeric code uniquely identifying this object
Object_Name
CharacterString
Alphanumeric string identifying this object
Object_Type
BACnetObjectType
Always: "BINARY_INPUT"
Present_Value
BACnetBinaryPV
Current value of this object: "ACTIVE" / "INACTIVE"
Description
CharacterString
Alphanumeric description of this object
Status_Flags
BACnetStatusFlags
Always: "{false, false, false, false}"
Event_State BACnetEventState
Always:
"NORMAL"
Out_Of_Service
BOOLEAN
Always: "false"
Binary_Input_BCID EtcBACnetCID
Unique
16
byte identifier assigned by P-CCS