Unison Paradigm BACnet Interface Object Reference Guide

1 - Object Types

The Paradigm Central Control Server (P-CCS) BACnet interface provides twelve (12)

object types; four (4) of them are standard BACnet object types and eight (8) of are ETC

proprietary object types.

This document section provides user detailed information for the construction of each of

these client readable object types.

1.1 Analog Input Object Type

Analog Input: BACnet Properties List

Is the Object Type Proprietary?

No, Compliant with Clause 12.2 of ASHRAE Standard BACnet 135-2004 document.

Does the Object Type contain any Proprietary Properties?

Yes, the “Analog_Input_BCID” property.

General Description of the Object Type

Analog Input objects are only created by the Paradigm Central Control Server (P-CCS)

based on the LightDesigner configuration and may be used to provide general user-defined

analog feedback for objects within a Paradigm system

Each object instance for the specified "Object_Type" has an "Object_Identifier" that is

unique for the type and "Object_Name".

The BACnet object instance is managed by the P-CCS, based on the configuration using

Paradigm LightDesigner software. An "Analog Input" object is created for each "Level"

object with functional assignment on the BACnet I/O panel within LightDesigner, up to a

maximum of 1000 objects.

The “Present_Value” property will always have the objects analog value represented as an

integer between the values of 0-255. The “Present_Value” is read-only and is not

changeable by the BACnet client.

The Analog Input "ETCBACnetCID" (Analog_Input_BCID) property will be provided a value

that is unique within the storage of the BACnet Interface device and the P-CCS sub-system.

Property Identifier

Property Datatype

Property Brief Description

Object_Identifier

BACnetObjectIdentifier

Numeric code uniquely identifying this object

Object_Name

CharacterString

Alphanumeric string identifying this object

Object_Type

BACnetObjectType

Always: "Analog_Input"

Present_Value

REAL

Current real value of this analog object

Priority_Array

BACnetPriorityArray

Read-only array of prioritized values

Relinquish_Default

REAL

Default "Present_Value" when all controll is null.

Description

CharacterString

Alphanumeric description of this object

Status_Flags

BACnetStatusFlags

Always: "{false, false, false, false}"

Event_State

BACnetEventState

Always: "NORMAL"

Out_Of_Service BOOLEAN

Always:

"false"

Units

BACnetEngineeringUnits

N/A

Analog_Input_BCID

EtcBACnetCID

Unique 16 byte identifier assigned by P-CCS