5.11. Setting Up Digital Inputs
The Protocol 3 controller can be run by external inputs wired to the controller from an external
source such as a PLC or switches on a control panel (Figure 21 displays standard digital input
wiring).
Enable Digital Inputs through the
Profile Menu
, then
General Configuration
and set
Remote
Profile Control
to
Enable
.
While the Remote Profile Control is enabled, profiles can be run
only by digital inputs (versus running profiles from the Profile
Mode).
The external run operation can
Run
,
Hold
or
Stop
profiles indexed in positions 1-7 in the
memory of the control. Table 19 shows the profile selection.
Table 19. Input settings.
Input 1
Input 2
Input 3
Index Selection
ON
OFF
OFF
1
OFF
ON
OFF
2
ON
ON
OFF
3
OFF
OFF
ON
4
Figure 21. Standard Digital Input Wiring.