Item
Description
Linear DC
Resolution:
8 bits in 250mS (10 bits in 1s typical, >10 bits in >1s typical)
Accuracy:
±0.25% of range, (mA @ 250W, V @ 2kW). Degrades linearly
to ±0.5% for increasing burden (to specification limits)
Isolation:
Basic Isolation
Table 3. Operating Conditions (For indoor use).
Item
Description
Temperature:
Operating: 0°C to 55°C (32
°F to 131°F)
Storage:
–20°C to 80°C (-4°F to 176°F)
Relative Humidity:
20% to 95% non
‐condensing
Supply Voltage and
Power:
100 to 240VAC ±10%, 50/60Hz, 20VA
Table 4. Conformance Norms.
Item
Description
EMI:
CE: Complies with EN61326
Safety Considerations:
CE: Complies with EN61010
‐1. UL, cUL to UL61010C‐1.
Pollution Degree 2, Installation Category II
Front Panel Sealing:
IP65 rating. IP20 behind the panel. (IP rating not recognized /
approved by UL)
Front Panel Cleaning:
Wash with warm soapy water and dry immediately. Close the
USB cover (if fitted) before cleaning.
Table 5. Display.
Item
Description
Display Type:
160 x 80 pixel, monochrome graphic LCD with a dual color
(red/green) backlight
Display Area:
66.54mm (W) x 37.42mm (H)
Display Characters:
0 to 9, a to z, A to Z, plus ( )
‐ and _