background image

Protocol 3 Controller

Owner’s Manual

W

ORKING WITH

O

PERATING

M

ODES

Version 1.2

47

Copyright © 2013 by Despatch Industries.

All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.

Table 15. Configuration Menu in Tabular Format.
Config-
uration
Menu

Description

Function

Available Settings

Input

Provide
primary
control and
high limit
settings

Control Input
Setup

Input Type: Thermocouples, PtRh, PT100,

NI120, amperages, voltages

Engineering Units:

°C, °F, °K, bar, %, %RH, pH,

psi or none

Decimal Point Position: Nearest 1/10 or 1/100

for DC inputs

Scale Input Range (lower and upper limits):

Min & Max range. Minimum range by default.

Input Filter Time: OFF-100 Sec

Cold Junction Compensation: Disable/Enable

Control Input
Calibration

Factory Calibration:

Single Point Calibration: OFF, -400-+400°

Two Point Calibration: Low Temp. Low Offset,

High Temp, High offset

High Limit
Input Setup

Input Type: Thermocouples, PtRh, PT100,

NI120, amperages, voltages

Engineering Units:

°C, °F, °K, bar, %, %RH, pH,

psi or none

Decimal Point Position: Nearest 1/10 or 1/100

for DC inputs

Scale Input Range (lower and upper limits): Min

& Max range

Input Filter Time: OFF-100 Sec

High Limit
Input
Calibration

High Limit Process Variable: -250

Factory Calibration: Resets back to factory

defaults

Single Point Calibration: OFF, -400-+400°

Two Point Calibration: Low Temp, Low Offset,

High Temp, High Offset

Control

Set control
actions, PID
control
options and
setpoint
limits

Primary Action
Control

Reverse Action /Direct Action: Reverse applies

primary power when below setpoint

Primary Proportional Band: From ON-Off

control or set width of band from 0.1 to 999.9

Integral Time (Auto-Reset): 1 sec to 99 min 59

sec or OFF

Derivative Time (Rate):

1 sec to 99 min 59 sec

or OFF

Primary Cycle Time: 0.5 sec to 512 sec

Primary Power Upper Limit: Minimum primary

power from 1 to 99% available power. Value
must be higher than the lower limit.

Primary Power Lower Limit: Maximum primary

power from 10 to 100% available power. Value
must be lower than the upper limit.

Setpoint Upper Limit: Maximum allowed control

setpoint

Setpoint Lower Limit: Minimum allowed control

setpoint