Table 16. configuration menu in tabular format, Table 15 – Despatch Protocol 3 Controller User Manual
Page 47
Protocol 3 Controller
Owner’s Manual
W
ORKING WITH
O
PERATING
M
ODES
Version 1.2
47
Copyright © 2013 by Despatch Industries.
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
Table 15. Configuration Menu in Tabular Format.
Config-
uration
Menu
Description
Function
Available Settings
Input
Provide
primary
control and
high limit
settings
Control Input
Setup
Input Type: Thermocouples, PtRh, PT100,
NI120, amperages, voltages
Engineering Units:
°C, °F, °K, bar, %, %RH, pH,
psi or none
Decimal Point Position: Nearest 1/10 or 1/100
for DC inputs
Scale Input Range (lower and upper limits):
Min & Max range. Minimum range by default.
Input Filter Time: OFF-100 Sec
Cold Junction Compensation: Disable/Enable
Control Input
Calibration
Factory Calibration:
Single Point Calibration: OFF, -400-+400°
Two Point Calibration: Low Temp. Low Offset,
High Temp, High offset
High Limit
Input Setup
Input Type: Thermocouples, PtRh, PT100,
NI120, amperages, voltages
Engineering Units:
°C, °F, °K, bar, %, %RH, pH,
psi or none
Decimal Point Position: Nearest 1/10 or 1/100
for DC inputs
Scale Input Range (lower and upper limits): Min
& Max range
Input Filter Time: OFF-100 Sec
High Limit
Input
Calibration
High Limit Process Variable: -250
Factory Calibration: Resets back to factory
defaults
Single Point Calibration: OFF, -400-+400°
Two Point Calibration: Low Temp, Low Offset,
High Temp, High Offset
Control
Set control
actions, PID
control
options and
setpoint
limits
Primary Action
Control
Reverse Action /Direct Action: Reverse applies
primary power when below setpoint
Primary Proportional Band: From ON-Off
control or set width of band from 0.1 to 999.9
Integral Time (Auto-Reset): 1 sec to 99 min 59
sec or OFF
Derivative Time (Rate):
1 sec to 99 min 59 sec
or OFF
Primary Cycle Time: 0.5 sec to 512 sec
Primary Power Upper Limit: Minimum primary
power from 1 to 99% available power. Value
must be higher than the lower limit.
Primary Power Lower Limit: Maximum primary
power from 10 to 100% available power. Value
must be lower than the upper limit.
Setpoint Upper Limit: Maximum allowed control
setpoint
Setpoint Lower Limit: Minimum allowed control
setpoint