If the display on the control read 200 °C and the actual temperature measured was 195°C

Enter the following settings for Two Point Calibration:

o Calibration Low Temp = 100, Calibration Low Offset = -1
o Calibration High Temp = 200, Calibration High Offset = -5

Return to the Main Menu by simultaneously pressing

and

.


5.6.3. Setting Up Remote Communication

Remote communication between the Protocol 3 controller and a PC running the Despatch
Protocol Manager software involves providing each controller with a unique address and
following the communication protocol procedures. Up to 32 separate controllers can be run from
a PC running the Despatch Protocol Manager software. See the Protocol Manager Instruction
Manual for the complete set-up procedure.


5.7. Automatic Tuning


Despatch does not recommend the use of Automatic Tuning. In
most oven applications, standard configuration has been
optimized.

Access

Automatic

Tuning

through the Main Menu (Section 5.2.4). The

Automatic

Tuning

menu displays all the auto

‐tuning options provided in the unit. Table 17 provides

additional information of each option.

1. Simultaneously press

and

.

2. Navigate to

Automatic

Tuning

using

.

3.

Press

to

Enter Automatic Tuning Mode Unlock Code.

4. Press

to reach

0010

,

the Mode Unlock Code.

5. Press

to step through and accept all automatic tune options.


To manually tune the controller, refer to

Control Configuration

in the

Configuration Menu

(

Section 5.6

)

.

Table 17. Automatic Tuning Options.
Menu Item

Description

Pre-Tune

A “single

‐shot” routine that disengages when complete.

Self-Tune

Continuous tuning routine that must be manually disengaged.