Setting up remote communication, Automatic tuning, Table 17. automatic tuning options – Despatch Protocol 3 Controller User Manual
Page 56
W
ORKING WITH
O
PERATING
M
ODES
Protocol 3 Controller
Owner’s Manual
56
Version 1.2
Copyright © 2013 by Despatch Industries.
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
If the display on the control read 200 °C and the actual temperature measured was 195°C
Enter the following settings for Two Point Calibration:
o Calibration Low Temp = 100, Calibration Low Offset = -1
o Calibration High Temp = 200, Calibration High Offset = -5
Return to the Main Menu by simultaneously pressing
and
.
5.6.3. Setting Up Remote Communication
Remote communication between the Protocol 3 controller and a PC running the Despatch
Protocol Manager software involves providing each controller with a unique address and
following the communication protocol procedures. Up to 32 separate controllers can be run from
a PC running the Despatch Protocol Manager software. See the Protocol Manager Instruction
Manual for the complete set-up procedure.
5.7. Automatic Tuning
Despatch does not recommend the use of Automatic Tuning. In
most oven applications, standard configuration has been
optimized.
Access
Automatic
Tuning
through the Main Menu (Section 5.2.4). The
Automatic
Tuning
menu displays all the auto
‐tuning options provided in the unit. Table 17 provides
additional information of each option.
1. Simultaneously press
and
.
2. Navigate to
Automatic
Tuning
using
.
3.
Press
to
Enter Automatic Tuning Mode Unlock Code.
4. Press
to reach
0010
,
the Mode Unlock Code.
5. Press
to step through and accept all automatic tune options.
To manually tune the controller, refer to
Control Configuration
in the
Configuration Menu
(
Section 5.6
.
Table 17. Automatic Tuning Options.
Menu Item
Description
Pre-Tune
A “single
‐shot” routine that disengages when complete.
Self-Tune