Table 12. Profile Setup Steps, Options and Descriptions.
Step # Protocol 3 Descriptor

Option

Description

General Configuration

1.

Remote Profile Control

Disabled

Disallow a remote source to run a profile

Enabled

Allow a remote source to run a profile

2.

Automatic Start

Disabled

Disallow use of delayed start time

Enabled

Allow controller to start at a later time with
programmed delay

Create a Profile

3.

Enter a Profile Name

Unique name for each profile using up to 8
characters

4.

Profile Start Trigger

None

Profile start not delayed

After Delay

Set hours and minutes to delay before
starting the profile

Day and Time

Set time of day (hour and minutes) and day
of week to start profile. Options include
each day of the week and combinations of
days.

5.

Profile Recovery
Method

If power-down occurs while this profile is
running, specify the action for the controller
to take during power-up:

Control Off

Controller goes to OFF

Restart Profile

Controller restarts current profile

Maintain Last
Profile SP

Controller maintains previous profile
setpoint

Continue
Profile

Controller continues (for specified time) the
profile from where it was when power
failed.

Profile Abort Action

If program aborts, profile should:

Control Off

Controller goes off

6.

Maintain Last
Profile SP

Choose the number of times to cycle the
program, up to an infinite number of times.

Edit a Profile Segment

7.

Edit Segment Number

Ramp Time

Set target setpoint (degrees centigrade)

Set the segment ramp time (hh:mm:ss)

Set the Auto-Hold Type: None, Above

Setpoint, Below Setpoint, Band.

Set Events 1-5: Press

or

to

toggle between Active and Inactive.

8.

Ramp Rate

Set the target setpoint (degrees

centigrade)

Set the segment ramp rate in units per

hour

Set the Auto-Hold Type: None, Above

Setpoint, Below Setpoint, Band.

Set Events 1-5: Press

or

to

toggle between Active and Inactive.

9.

Step

Set the target setpoint (degrees centigrade)

10.

Dwell

Choose time to dwell at setpoint.

Specify Auto-Hold type: None, Above
setpoint, Below setpoint, Band