beautypg.com

Snorkel TL39T User Manual

Page 33

background image

Rev C

page 5-1

RCD/ELCB Outlet (option)

Figure 5.1 - RED/ELCB Outlet

The RCD (Residual Current Device) is located at

the base and will protect against short circuits to

earth. When there is a short circuit the RCD will

shut down the 230v AC power to the platform outlet.
To reset the outlet disconnect the power tool lead

from the platform box and reset the RCD at the

base.
If the problem persists call a trained service

technician.

Main Circuit Breaker

Figure 5.2 - Main Circuit Breaker

There is only one circuit breaker, on a standard

TL39T, that is accessible to the operator. Its

purpose is to protect the electrical circuits from

electrical overloads. When the circuit breaker trips

(pops out) push it back in then attempt to use the

TL39T. If the circuit breaker trips a second time,

take the TL39T out of service and refer the problem

to a qualified trained service technician for repair.

Stabilisers

Figure 5.3 - Stabilisers

The TL39T booms cannot be raised unless the

stabilisers are set and the lift enable light on the

lower control box is lit. Once the booms are raised

from the stowed position the stabilisers become

disabled until the booms are stowed in the travel

position.

5. Shut-offs and Circuit Breakers