Safety, Danger, Safe operation – Snorkel TL39T User Manual
Page 13: Electrocution hazards, Minimum safe approach distance

Rev C
page 1-1
1. Safety
■
Safe Operation
Knowledge of the information in this manual, and
proper training, provide a basis for safely operating
the TL39T. Know the location of all the controls and
how they operate to act quickly and responsibly in
an emergency.
Safety devices reduce the likelihood of an accident.
Never disable, modify, or ignore any safety device.
Safety alerts in this manual indicate situations
where accidents may occur.
If any mal function, hazard or potentially unsafe
condition relating to capacity, intended use, or safe
operationis suspected, stop the operation of the
MHP and seek assistance.
The operator bears ultimate responsibility for
following all manufacturers instructions and
warnings, regulations and safety rules of their
employer and/or any country or regional law.
■
Electrocution Hazards
The TL39T is an all metal boom aerial work
platform and
is not electrically insulated.
Do not operate it near electrical conductors.
Regard all conductors as being energized.
Do not operate out side during a thunderstorm.
❑
Minimum safe approach distance
Minimum safe approach distances to energised
power lines and their associated parts must be
observed wile operating the MHP.
Figure 1 - Minimum Safe Approach Distance
ANSI A92.5
!
DANGER
The MHP is not electrically insulated. Death
or serious injury can result from contact with,
or inadequate clearance from, an energised
conductor.
Do not go closer than the minimum safe
approach distance.
ANSI publications define minimum distances that
must be observed when working near bus bars
and energised power lines. Figure 1 and Table 1
are reprinted courtesy of the Scaffold industry
Association, ANSI/SIA A92.5.
Voltage Range
(Phase to Phase
Minimum Safe Approach
Distance
Feet
Metres
0 to 300V
Avoid Contact
Over 300V to 50kV
10
3.05
Over 50kV to 200kV
15
4.60
Over 200kV to 350kV
20
6.10
Over 350kV to 500kV
25
7.62
Over 500kV to 750kV
35
10.7
Table 1 - Minimum Safe Approach Distance
ANSI 92.5
Australian Standard AS2550.10 defines minimum
distances that must be observed when working near
live aerial conductors up to and including 133kV
(see Figure 2).
Figure 2 - Minimum Safe Approach Distance
AS 2550.10
Denotes prohibited zone
Caution: - Diagrams shown are only for purposes of illustrating
M.S.A.D. Work positions, not all work positions.
6.4
6.4
3
3
n
CLEARANCES FROM LIVE AERIAL CONDUCTORS
(Dimensions are in metres)
Spotter
required
zone
No go zone
Sag
Variations
in Sag
Personal
protection
barriers
FRONT VIEW
SIDE VIEW
Distribution Lines Up to and Including 133kV