8

Figure : Clearance to Combustible Materials

5. For boiler located in an

unconfined space in a

building of other than unusually tight construction,

adequate combustion and ventilation air is normally

provided by fresh air infiltration through cracks

around windows and doors.

6. For boiler located within unconfined space in

building of unusually tight construction or within

confined space, provide outdoor air through two

permanent openings which communicate directly or

by duct with the outdoors or spaces (crawl or attic)

freely communicating with the outdoors. Locate one

opening within 12 inches of top of space. Locate

remaining opening within 12 inches of bottom of

space. Minimum dimension of air opening is 3

inches. Size each opening per following:

a. Direct communication with outdoors. Minimum

free area of 1 square inch per 4,000 Btu per hour

input of all equipment in space.

b. Vertical ducts. Minimum free area of 1 square

inch per 4,000 Btu per hour input of all

equipment in space. Duct cross-sectional area

shall be same as opening free area.

c. Horizontal ducts. Minimum free area of 1 square

inch per 2,000 Btu per hour input of all

equipment in space. Duct cross-sectional area

shall be same as opening free area.

Alternate method for boiler located within confined

space. Use indoor air if two permanent openings

communicate directly with additional space(s) of

sufficient volume such that combined volume of all

spaces meet criteria for unconfined space. Size each

opening for minimum free area of 1 square inch per

1,000 Btu per hour input of all equipment in spaces,

but not less than 100 square inches.

7. Ventilation Duct Louvers and Grilles. Equip outside

openings with louvers to prevent entrance of rain

and snow, and screens to prevent entrance of insects

and rodents. Louvers and grilles must be fixed in

open position or interlocked with equipment to open

automatically before burner operation. Screens must

not be smaller than ¼ inch mesh.

Consider the blocking effect of louvers, grilles and

screens when calculating the opening size to provide

the required free area. If free area of louver or grille

is not known, assume wood louvers have 20-25

percent free area and metal louvers and grilles have

60-75 percent free area.

H.

Do not install boiler where gasoline or other flammable

vapors or liquids, or sources of hydrocarbons (i.e.

bleaches, cleaners, chemicals, sprays, paint removers,

fabric softeners, etc.) are used or stored.