M.

Excessive Make-Up Water

CAUTION

IF, DURING NORMAL OPERATION, IT IS

NECESSARY TO ADD MORE WATER THAN

INDICATED BELOW, CONSULT A QUALIFIED

SERVICE TECHNICIAN TO CHECK YOUR SYSTEM

FOR LEAKS.

Model No.

Gallons Per

Month

Gallons Per

Year

IN3

0.1

1

IN4

0.1

1

IN5

0.2

2

IN6

0.2

2

IN7

0.2

3

IN8

0.2

3

IN9

0.3

3

IN10

0.3

4

IN11

0.3

4

IN12

0.4

4

A leaky system will increase the volume of make-up

water supplied to the boiler, which can significantly

shorten the life of the boiler. Entrained in make-up

water are dissolved minerals, salts, and oxygen. When

the fresh, cool make-up water is heated in the boiler, the

minerals fall out as sediment, the salts coat the inside of

the boiler, and the oxygen escapes as a gas. The

accumulation of sediment eventually isolates the water

from contacting the cast iron. When this happens the

cast iron in that area gets extremely hot and eventually

cracks. The presence of free oxygen or chloride slats in

the boiler corrodes the cast iron from the inside. More

make-up water and higher concentrations of contami-

nants damage the boiler sooner. Our warranty does

not cover corrosion and sediment-related damage.

Clearly it is in everyone's best interest to prevent this

type of failure. You can do your part by ensuring that

your system is leak-free, keeping leakage to less than 2

percent of the total water volume each month.