h. Follow instructions TO TURN OFF GAS TO

APPLIANCE. See Figure 48, 49, 50, or 51.

Drain boiler and system piping.

i. Remove drain valve. Thoroughly wash boiler

water passages with high pressure spray through

drain valve tapping.

j. Fill boiler to normal waterline. If water in gauge

glass is not clear, repeat procedure starting at

step b.

k. Remove surface blow-off piping. Install 1 NPT

plug in Tapping "L". See Figure 2.

4. Add Boiler Water Treatment.

a. Remove safety valve.
b. Pour recommended compound into boiler

through safety valve opening.

c. Reinstall safety valve in Tapping "E" with

spindle in vertical position. See Figures 1 and 2.

d. Follow Lighting or Operating Instructions to

place boiler in operation. See Figure 48, 49, 50,

or 51.

e. Boil water or heat water to 180°F.
f. Measure boiler water alkalinity. pH should be

between 7 and 11. Add recommended water

treatment chemicals, if necessary, to bring the pH

within the specified range.

5. If unsteady water line, foaming or priming persist:

a. Follow Lighting or Operating Instructions to

place boiler in operation. See Figure 48, 49, 50,

or 51.

b. Install gate valve (shut-off valve) in Hartford

Loop. Install drain valves in return main and at

boiler. See Figure 23.

c. Connect hoses from drain valves to floor drain.

Close gate valve in Hartford Loop. Open drain

valve in return main.

d. Fill boiler to normal water line. Follow Lighting

or Operating Instructions to place boiler in

operation. See Figure 48, 49, 50, or 51.

e. Operate boiler for at least 30 minutes after

condensate begins to run hot. Follow instructions

TO TURN OFF GAS TO APPLIANCE. See

Figure 48, 49, 50, or 51.

f. Close all radiator valves. Remove all supply

main air valves. Plug openings in supply main.

g. Drain approximately 5 gallons of boiler water

into container. Mix in recommended boil-out

compound.

h. Remove safety valve. Pour recommended

compound into boiler through safety valve

opening. Reinstall safety valve in Tapping "E"

with spindle in vertical position. See Figures 1

and 2.

i. Follow Lighting or Operating Instructions to

place boiler in operation. See Figure 48, 49, 50,

or 51. Slowly feed water to boiler. Water will

rise slowly into supply main and back through

return main. Adjust flow to maintain

approximately 180°F water from return main

hose. Continue until water runs clear from hose

for at least 30 minutes.

j. Turn off water to boiler. Continue to operate until

excess water is removed from boiler and system

(by steaming) and boiler water reaches normal

waterline.

k. Follow instructions TO TURN OFF GAS TO

APPLIANCE. See Figure 48, 49, 50, or 51.

Open all radiator valves. Reinstall all supply

main air valves. Open gate valve in Hartford

Loop.

l. Allow boiler to cool until crown sheet is no

longer too hot to touch. Close drain valves at

boiler and in return main. Fill boiler slowly to

normal waterline.

m. Follow Lighting or Operating Instructions to

place boiler in operation. See Figure 48, 49, 50,

or 51. Allow boiler to steam for 10 minutes.

Drain one quart of water from lower Gauge

Glass fitting.

n. Drain second quart sample from lower Gauge

Glass fitting. If sample is not clear, repeat cycle

of draining boiler and return main and refilling

boiler until sample is clear.

o. If after normal operation boiler water becomes

dirty from additional system piping sediment

returning to boiler.
i. Complete steps 5a through 5n.

ii. Complete steps 3a through 3k.

6. Make pH or Alkalinity Test.

a. After boiler and system have been cleaned and

refilled as previously described, test the pH of

the water in the system. This can easily be done

by drawing a small sample of boiler water and

testing with Hydrion paper which is used in the

same manner as litmus paper, except it gives

specific readings. A color chart on the side of the

small Hydrion dispenser gives the reading in pH.

Hydrion paper is inexpensive and obtainable

from any chemical supply house or through your

local druggist. The pH should be higher than 7

but lower than 11. Add recommended water

treatment chemicals, if necessary, to bring the pH

within the specified range. With this lower level

of protection, care must be exercised to eliminate

all of the free oxygen in the system.

b. Boiler is now ready to be put into service.

N.

Clean Heating System (Water). A local qualified

water treatment chemical specialist is a suggested

source for recommendations regarding appropriate

chemical compounds and concentrations which are

compatible with local environmental regulations.