Water Boiler with Continuous Ignition (Standing Pilot)

and Tankless Heater. See Figure 43.
1. Normal Operation

a. Thermostat calls for heat or low limit senses

water temperature below set point.

b. Vent Damper (if used) opens as stated in Vent

Damper Sequence of Operation.

c. Gas Valve(s) is energized allowing main gas flow

and ignition of Main Burners.

d. After Thermostat or low limit is satisfied Gas

Valve(s) is de-energized, extinguishing main

flame. Vent Damper (if used) closes.

2. Safety Shutdown

a. Limit: Automatically interrupts main burner

operation when water temperature exceeds set

point. Maximum allowable temperature is 250°F.

Normal operation resumes when water

temperature falls below set point.

b. Blocked Vent Switch. Automatically interrupts

main burner operation when excessive vent

system blockage occurs. Control is a multiple

use device. If blocked vent switch is activated do

not attempt to place boiler in operation. Correct

source of blockage and reset blocked vent

switch.

c. Flame Roll-out Switch. Automatically interrupts

boiler operation when flames or excessive heat

are present in vestibule. Control is single use

device. If flame roll-out switch is activated do

not attempt to place boiler in operation. Correct

source of blockage and replace flame roll-out

switch.

d. Thermocouple: senses pilot flame and causes gas

valve to turn off main burner and pilot burner gas

flow should pilot burner flame extinguish.