beautypg.com

I. pre-installation, Warning, Danger – Burnham Independence IN10 User Manual

Page 7: Notice

background image

I. Pre-Installation

A.

Inspect shipment carefully for any signs of damage. All

equipment is carefully manufactured, inspected and

packed. Our responsibility ceases upon delivery of

boiler to carrier in good condition. Any claim for

damage or shortage in shipment must be filed

immediately against carrier by consignee. No claims for

variances or shortages will be allowed by Boiler

Manufacturer, unless presented within sixty (60) days

after receipt of equipment.

B.

Installation must conform to the requirements of the

authority having jurisdiction. In the absence of such

requirements, installation must conform to the National

Fuel Gas Code, NFPA 54/ANSI Z223.1 and/or CAN/

CSA B149.1 Installation Codes. Where required by the

authority having jurisdiction, the installation must

conform to the Standard for Controls and Safety

Devices for Automatically Fired Boilers, ANSI/ASME

No. CSD-1.

C.

Appliance is design certified for installation on

combustible flooring. Boiler must not be installed on

carpeting.

D.

Provide clearance between boiler jacket and

combustible material in accordance with local fire

ordinance. See Figure 3 for minimum listed clearance

to combustible material. Recommended service

clearance is 24 inches from left side, right side, and

front. Additional clearance may be required on left side

if optional tankless heater is installed. Service

clearances may be reduced to minimum clearances to

combustible materials.

E.

Install boiler on level floor as close to chimney as

possible. For basement installation provide a solid base,

such as concrete, steel or masonry if floor is not level or

if water may be encountered on floor around boiler.

F.

Protect gas ignition system components from water

(dripping, spraying, rain, etc.) during boiler operation

and service (circulator replacement, control

replacement, etc.).

G.

Provide combustion and ventilation air in accordance

with applicable provisions of local building codes, or

the National Fuel Gas Code, NFPA 54/ANSI Z223.1,

Section 5.3, Air for Combustion and Ventilation; or

CAN/CSA B149.1 Installation Code.

WARNING

Adequate combustion and ventilation air must be

provided to assure proper combustion.

The following guideline is based on the National Fuel

Gas Code, NFPA 54/ANSI Z223.1.
1. Determine volume of space (boiler room). Rooms

communicating directly with space (through

openings not furnished with doors) are considered

part of space.

Volume [ft³] = Length [ft] x Width [ft] x Height [ft]
2. Determine Total Input of all appliances in space.

Round result to nearest 1,000 Btu per hour (Btuh).

3. Determine type of space. Divide Volume by Total

Input.
a. If result is greater than or equal to 50 ft³ per

1,000 Btuh, space is considered an unconfined

space.

b. If result is less than 50 ft³ per 1,000 Btuh, space

is considered a confined space.

4. Determine building type. A building of unusually

tight construction has the following characteristics:
a. Walls and ceiling exposed to outside atmosphere

have a continuous water vapor retarder with a

rating of 1 perm or less with openings gasketed

and sealed, and

b. Weather-stripping has been added on openable

windows and doors, and

c. Caulking or sealants applied in joints around

window and door frames, between sole plates

and floors, between wall-ceiling joints, between

wall panels, at plumbing and electrical

penetrations, and at other openings.

WARNING

If you do not follow these instructions exactly,

a fire or explosion may result causing property

damage or personal injury.

DANGER

Do not install boiler where gasoline or other

flammable vapors or liquids, or sources of

hydrocarbons (i.e. bleaches, cleaners, chemicals,

sprays, paint removers, fabric softeners, etc.) are

used or stored.

NOTICE

Due to the low water content of the boiler, mis-

sizing of the boiler with regard to the heating

system load will result in excessive boiler cycling

and accelerated component failure. Burnham

DOES NOT warrant failures caused by mis-sized

boiler applications. DO NOT oversize the boiler

to the system.

This manual is related to the following products: