X. Service Instructions

A.

General. Inspection and service should be conducted

annually, except as noted. Turn off electrical power and

gas supply while conducting service or maintenance.

Follow instructions TO TURN OFF GAS TO

APPLIANCE. See Figures 48, 49, 50 or 51.

B.

Maintenance of Low Water Cutoff

1. McDonnell & Miller PS-802 or Hydrolevel

CycleGard CG400 Probe Style Only.
a. Drain boiler to point below Tapping 'K'. See

Figure 2.

b. Disconnect wire(s) connecting control and probe.
c. Remove control from probe.

DANGER

Assure that the boiler is at zero pressure before

removing the LWCO probe. Do not rely on the

pressure gauge to indicate that the boiler is at

zero pressure. Open the safety valve to relieve

all internal pressure prior to proceeding. Safety

valve discharge piping must be piped such that

the potential for burns is eliminated.

d. Unscrew probe from Tapping 'K'. Inspect for

scale and sediment buildup.

e. Remove light deposits with damp cloth soaked

with vinegar.

f. Remove stubborn deposits using diluted

phosphoric acid (H

2

PO

4

) solution, 3 parts water

to 1 part phosphoric acid. Normal operation will

occur with up to 0.2 inch of contamination. If

scale or contamination exceeds 0.2 inches, clean

probe more frequently.

g. Clean Tapping 'K' to remove old pipe dope and

other foreign matter.

h. Apply moderate amount of good quality pipe

dope to probe threads, leaving two end threads

bare. Install probe in Tapping 'K'. Mount control

on probe. Attach wire(s) between control and

probe.

i. Fill boiler to normal waterline. Add water

treatment as needed.

2. McDonnell & Miller 67 Float Style Only.

a. Weekly (or more frequently if necessary). Open

blow-off valve to flush sediment chamber.

Follow instructions on Blow-Down Card affixed

to Jacket adjacent to low water cutoff.

b. Annually. Dismantle to extent necessary to

remove obstructions and insure proper function

of working parts.

DANGER

This boiler uses flammable gas, high voltage electricity, moving parts, and very hot water under high

pressure. Assure that all gas and electric power supplies are off and that the water temperature is cool

before attempting any disassembly or service.

Assure that all gas valves and electrical disconnect switches are off before attempting any disassembly

or service.
Do not attempt any service work if gas is present in the air in the vicinity of the boiler. Never modify,

remove or tamper with any control device.

WARNING

This boiler must only be serviced and repaired by skilled and experienced service technicians.
If any controls are replaced, they must be replaced with identical models.
Read, understand and follow all the instructions and warnings contained in all the sections of this

manual.
If any electrical wires are disconnected during service, clearly label the wires and assure that the wires

are reconnected properly.
Never jump out or bypass any safety or operating control or component of this boiler.
Read, understand and follow all the instructions and warnings contained in ALL of the component

instruction manuals.
Assure that all safety and operating controls and components are operating properly before placing

the boiler back in service.