5

Figure 57: 1" Main Burner Flame

Figure 53: Pilot Burner Flame, Honeywell Q350

Figure 55: Pilot Burner Flame, Honeywell Q348

Figure 54: Pilot Burner Flame, Honeywell Q327

Figure 56: 40mm Main Burner Flame

F.

Check pilot burner flame and main burner flames

through observation port.
1. Check pilot flame.

a. Continuous Ignition (Standing Pilot), Models

IN3 through IN7. See Figure 53. Pilot burner

produces a single flame. Flame should be steady,

medium hard blue enveloping 3/8 to ½ inch of

thermocouple.

b. Continuous Ignition (Standing Pilot), Models

IN8 through IN12. See Figure 54. Pilot burner

produces three (3) flames. Center flame should

be steady, medium hard blue enveloping 3/8 to ½

inch of thermocouple.

c. Electronic Ignition (EI), Models IN3 through

IN12. See Figure 55. Pilot should be lit only

after completing Step 3. Pilot burner produces

three (3) flames. Center flame should be steady,

medium hard blue enveloping 3/8 to ½ inch of

sensing probe.

CAUTION

Avoid operating this boiler in an environment

where saw dust, loose insulation fibers, dry wall

dust, etc. are present. If boiler is operated under

these conditions, the burner interior and ports

must be cleaned and inspected daily to insure

proper operation.