beautypg.com

Caution, Warning – Burnham Independence IN10 User Manual

Page 58

background image

58

2. Adjust thermostat to highest setting.
3. Check main burner flames. See Figure 56 or 57.

Flame should have clearly defined inner cones with

no yellow tipping. Orange-yellow streaks caused by

dust should not be confused with true yellow

tipping.

4. Adjust thermostat to normal setting.

G.

Check thermostat operation. Raise and lower

temperature setting to start and stop boiler operation.

H.

Check ignition system shutoff. Gas valve should close

and pilot and main burners extinguish.
1. Continuous Ignition (Standing Pilot): disconnect

thermocouple from gas valve.

2. Electronic Ignition (EI): disconnect igniter/sensor

cable from ignition module terminal "9".

I.

Check low water cutoff (steam only).

1. Adjust thermostat to highest setting.
2. With boiler operating, open drain and slowly drain

boiler.

CAUTION

Do not drain below gauge glass.

3. Main burners will extinguish when water level drops

below low water cutoff. Water should still be visible

in gauge glass. Verify limit, thermostat or other

controls have not shut off boiler.

4. Adjust thermostat to lowest setting. Refill boiler to

normal water line.

J.

Check Limit.

1. Adjust thermostat to highest setting.
2. Steam: Observe pressure gauge. When pressure is

indicated, adjust limit to setting below observed

pressure. Main burners should extinguish.

WARNING

Failure to properly adjust gas input rate will result

in over firing or under firing of the appliance.

Improper and unsafe boiler operation may result.

3. Water: Observe temperature gauge. When

temperature exceeds limit set point main burners

should extinguish.

4. Adjust limit to setting above observed reading. Main

burners should reignite.

5. Adjust thermostat to lowest setting. Adjust limit to

desired setting.

K.

Adjust gas input rate to boiler. Natural Gas.

1. Adjust thermostat to highest setting.
2. Check manifold gas pressure. Manifold pressure is

listed on Rating Label.
a. Models IN3-IN12 with Standing Pilot, IN3-IN9

with Hot Surface to Pilot and IN3-IN11 with

Electronic Ignition. Adjust gas valve pressure

regulator as necessary (turn adjustment screw

counterclockwise to decrease manifold pressure,

or clockwise to increase manifold pressure). If

pressure can not be attained, check gas valve

inlet pressure. If less than minimum gas supply

pressure listed on Rating Label, contact gas

supplier for assistance.

b. Model IN12 with Electronic Only.

i. Turn off gas valve not having pilot control.
ii. On gas valve with pilot control, adjust gas

valve pressure regulator to obtain required

manifold pressure, or if unattainable, highest

pressure without forcing adjustment screw

(turn adjustment screw counterclockwise to

decrease manifold pressure, or clockwise to

increase manifold pressure).

iii. Turn on gas valve not having pilot control.

Adjust gas valve pressure regulator to obtain

required manifold pressure. Manifold

pressure may not change during initial turns

of adjustment screw.

3. Clock gas meter for at least 30 seconds. Use Table

10 to determine gas flow rate in Cubic Feet per

Hour.

4. Determine Input Rate. Multiply gas flow rate by gas

heating value.

5. Compare measured input rate to input rate stated on

Rating Label.
a. Boiler must not be overfired. Reduce input rate

by decreasing manifold pressure. Do not reduce

more than 0.3 inch w.c. If boiler is still overfired,

contact your Governale distributor or Regional

Office for replacement Gas Orifice.

b. Increase input rate if less than 98% of Rating

Label input. Increase manifold gas pressure no

more than 0.3 inch w.c. If measured input rate is

still less than 98% of rated input:
i. Remove Main Burners per procedure in

Section X: Service Instructions.

ii. Remove gas orifices. Drill one (1) drill size

larger (drill size is stamped on orifice).

iii. Reinstall gas orifices and main burners.

Measure input rate.

6. Recheck Main Burner Flame.
7. Return other gas-fired appliances to previous

conditions of use.

This manual is related to the following products: