If a long term pressure test of the hydronic system is

required, the boiler should first be isolated to avoid a

pressure loss due to the escape of air trapped in the

boiler.

To perform a long term pressure test including the

boiler, ALL trapped air must first be removed from the

boiler.

A loss of pressure during such a test, with no visible

water leakage, is an indication that the boiler contained

trapped air.