Water Boiler with Intermittent Ignition (EI) and

Intermittent Circulation. See Figure 40.
1. Normal Operation

a. Thermostat calls for heat.
b. Vent Damper (if used) opens as stated in Vent

Damper Sequence of Operation.

c. Ignition Module is energized. Pilot Valve opens

and Igniter is energized to ignite Pilot Burner.

d. Sensor proves presence of pilot flame. Main

Valve(s) opens and ignites Main Burners.

e. After Thermostat is satisfied Ignition Module is

de-energized, extinguishing pilot and main

flame. Vent Damper (if used) closes.

2. Safety Shutdown

a. Limit: Automatically interrupts main burner

operation when water temperature exceeds set

point. Maximum allowable temperature is 250°F.

Normal operation resumes when water

temperature falls below set point.

b. Blocked Vent Switch. Automatically interrupts

main burner operation when excessive vent

system blockage occurs. Control is a multiple

use device. If blocked vent switch is activated do

not attempt to place boiler in operation. Correct

source of blockage and reset blocked vent

switch.

c. Flame Roll-out Switch. Automatically interrupts

boiler operation when flames or excessive heat

are present in vestibule. Control is single use

device. If flame roll-out switch is activated do

not attempt to place boiler in operation. Correct

source of blockage and replace flame roll-out

switch.

d. Igniter/Sensor: senses pilot flame and causes

ignition module to turn off main burner and pilot

burner gas flow should pilot burner flame

extinguish. Five to six minutes after shutdown,

Ignition Module restarts ignition sequence.

For Electronic Ignition Trouble Shooting Guide,

see Page 65. For LED Status Codes, see Tables

8 and 9 on pages 55 and 56.