Burnham Independence IN10 User Manual

Page 14

background image

14

Figure 20: Thermostat Isolation Relay Attachment

3.

All Steam Boilers and Water Boilers except

"EZW" and "WC" Controls Cartons
a. Install Junction Box. See Figure 19A.

i. Remove center knockout in rear of Junction

Box and insert black plastic snap bushing in

hole.

ii. Install mounting bracket to rear of Junction

Box with two (2) blunt sheet metal screws

provided.

iii. Align center and mounting holes of Junction

Box with upper front corner of jacket left

side panel.

iv. Install Junction Box to jacket from inside

vestibule area with two (2) blunt sheet metal

screws provided.

b. Mount transformer on Junction Box. For

Canadian boiler provide strain relief by loosely

securing Transformer to Junction Box with wire

tie inserted through Transformer plate and a

Junction Box mounting hole. See Figure 19B.

c. Fork connector on yellow wire of gas valve

harness must be removed and wire stripped

before making wire connections. Refer to

Section VIII for wiring.

d. Steam Boilers only. Secure the R8222

Thermostat Isolation Relay to upper left corner of

jacket vestibule panel with sheet metal screws

provided. See Figure 20.

e. Water with tankless heater only (EZWT and

WCT). Secure R8225D relay to Junction Box.

See Figure 1.

4. Water Boiler

a. Install Temperature/Pressure Gauge into upper

Tapping "C" (½ NPT bushed to ¼ NPT). See

Figure 1 and 2. Tighten by wrench applied to

square shank on back of gauge. DO NOT

APPLY PRESSURE ON GAUGE CASE since

this may destroy calibration of gauge.

Figure 19B: Junction Box and Transformer

Assembly

Figure 19A: Junction Box and Mounting Bracket

Assembly

b. Install hot water temperature limit and/or

combination control. Remove well from control.

Screw well into Tapping "H" (¾ NPT). See

Figure 1 and 2. Install bulb in well as far as

possible, then tighten set screw.

c. On boilers equipped with a circulator without

tankless heater in areas where condensation of

flue gases is encountered in boiler flueways, a

reverse-acting circulator control should be

installed in supply as close as possible to boiler

in order to avoid condensation.

E.

Continue to Section IV. Packaged Boiler Assembly,

Paragraph E.