beautypg.com

Burnham Independence IN10 User Manual

Page 55

background image

55

Table : Ignition Module Terminal Cross-Reference

Ignition Module

Terminal Designation

Wiring Ladder Diagram

Terminal Number

MV

1

MV/PV

2

PV

3

GND

4

24V (GND)

5

24V

6

SPARK

9

Figure 52: LED Locations

Yellow LED

Flash Code

a

Indicates

Recommended

Service Action

Heartbeat

Normal Flame Signal

N/A

2

Weak Flame Signal -

System will operate reliably but flame signal is

less than desired.

Note: This indication may flash temporarily

during or shortly after lightoff on some

applications.

Perform routine

maintenance to

assure optimum

flame signal.

1

Marginal Flame Signal (less than 1.1 µA) -

System may not operate reliably over time.

Service call recommended.

Note: This indication may flash temporarily

during or shortly after lightoff on some

applications.

Check gas supply,

pilot burner, flame

sense wiring,

contamination of

flame rod, burner

ground connection.

OFF

No Flame or Flame Signal -

below minimum threshold for system operation.

N/A

a

Flash Code Descriptions

- Heartbeat: Constant ½ second bright, ½ second dim cycles.
- The flash code number signifies that the LED flashes X times at 2Hz, remains

off for two seconds, and then repeats sequence.

TABLE 8: Yellow LED Flame Codes

This manual is related to the following products: