Burnham Independence IN10 User Manual
Page 55
55
Table : Ignition Module Terminal Cross-Reference
Ignition Module
Terminal Designation
Wiring Ladder Diagram
Terminal Number
MV
1
MV/PV
2
PV
3
GND
4
24V (GND)
5
24V
6
SPARK
9
Figure 52: LED Locations
Yellow LED
Flash Code
a
Indicates
Recommended
Service Action
Heartbeat
Normal Flame Signal
N/A
2
Weak Flame Signal -
System will operate reliably but flame signal is
less than desired.
Note: This indication may flash temporarily
during or shortly after lightoff on some
applications.
Perform routine
maintenance to
assure optimum
flame signal.
1
Marginal Flame Signal (less than 1.1 µA) -
System may not operate reliably over time.
Service call recommended.
Note: This indication may flash temporarily
during or shortly after lightoff on some
applications.
Check gas supply,
pilot burner, flame
sense wiring,
contamination of
flame rod, burner
ground connection.
OFF
No Flame or Flame Signal -
below minimum threshold for system operation.
N/A
a
Flash Code Descriptions
- Heartbeat: Constant ½ second bright, ½ second dim cycles.
- The flash code number signifies that the LED flashes X times at 2Hz, remains
off for two seconds, and then repeats sequence.
TABLE 8: Yellow LED Flame Codes