9

L.

Water Boiler with Continuous Ignition (Standing Pilot)

and Intermittent Circulation. See Figure 39.
1. Normal Operation

a. Thermostat calls for heat.
b. Vent Damper (if used) opens as stated in Vent

Damper Sequence of Operation.

c. Gas Valve(s) is energized allowing main gas flow

and ignition of Main Burners.

d. After Thermostat is satisfied Gas Valve(s) is de-

energized, extinguishing main flame. Vent

Damper (if used) closes.

2. Safety Shutdown

a. Limit: Automatically interrupts main burner

operation when water temperature exceeds set

point. Maximum allowable temperature is 250°F.

Normal operation resumes when water

temperature falls below set point.

b. Blocked Vent Switch. Automatically interrupts

main burner operation when excessive vent

system blockage occurs. Control is a multiple

use device. If blocked vent switch is activated do

not attempt to place boiler in operation. Correct

source of blockage and reset blocked vent

switch.

c. Flame Roll-out Switch. Automatically interrupts

boiler operation when flames or excessive heat

are present in vestibule. Control is single use

device. If flame roll-out switch is activated do

not attempt to place boiler in operation. Correct

source of blockage and replace flame roll-out

switch.

d. Thermocouple: senses pilot flame and causes gas

valve to turn off main burner and pilot burner gas

flow should pilot burner flame extinguish.