beautypg.com

Burnham Independence IN10 User Manual

Page 37

background image

K.

Steam Boiler with Intermittent Ignition (EI) and Float

Low Water Cutoff. See Figure 38.
1. Normal Operation

a. Thermostat calls for heat. Thermostat Isolation

Relay is energized, closing contacts.

b. Vent Damper (if used) opens as stated in Vent

Damper Sequence of Operation.

c. Ignition Module is energized. Pilot Valve opens

and Igniter is energized to ignite Pilot Burner.

d. Sensor proves presence of pilot flame. Main

Valve(s) opens and ignites Main Burners.

e. After Thermostat is satisfied Ignition Module is

de-energized, extinguishing pilot and main

flame. Vent Damper (if used) closes.

2. Safety Shutdown

a. Limit: Automatically interrupts main burner

operation when steam pressure exceeds set point.

Maximum allowable pressure is 15 psi. Normal

operation resumes when system pressure falls

below set point.

b. Low Water Cutoff (LWCO): Automatically

interrupts main burner operation when surface of

boiler water falls to lowest permissible operating

level. Normal operation resumes when water

returns to normal level.

c. Blocked Vent Switch. Automatically interrupts

main burner operation when excessive vent

system blockage occurs. Control is a multiple

use device. If blocked vent switch is activated do

not attempt to place boiler in operation. Correct

source of blockage and reset blocked vent

switch.

d. Flame Roll-out Switch. Automatically interrupts

boiler operation when flames or excessive heat

are present in vestibule. Control is single use

device. If flame roll-out switch is activated do

not attempt to place boiler in operation. Correct

source of blockage and replace flame roll-out

switch.

e. Igniter/Sensor: senses pilot flame and causes

ignition module to turn off main burner and pilot

burner gas flow should pilot burner flame

extinguish. Five to six minutes after shutdown,

Ignition Module restarts ignition sequence.

For Electronic Ignition Trouble Shooting Guide,

see Page 65. For LED Status Codes, see Tables

8 and 9 on pages 55 and 56.

This manual is related to the following products: