Table 4: Fitting Equivalent Lengths

Table 5: Specific Gravity Correction Factors for

Natural Gas

4. All above ground gas piping upstream from manual

gas valve must be electrically continuous and

bonded to a grounding electrode. Do not use gas

piping as a grounding electrode. Refer to the

National Electrical Code, ANSI/NFPA 70 and/or

CSA C22.1 Electrical Code.

C.

Pressure Test. The boiler and its gas connection must

be leak tested before placing boiler in operation.
1. Protect boiler gas valve. For all testing over ½ psig,

boiler an its individual shut-off valve must be

disconnected from gas supply piping. For testing at

½ psig or less, isolate boiler from gas supply piping

by closing boiler's individual manual shut-off valve.

2. Using soap solution, or similar non-combustible

solution, electronic leak detector or other approved

method. Check that boiler gas piping valves, and all

other components are leak free. Eliminate any

leaks.

Table 3: Maximum Capacity of Schedule 40 Pipe in CFH for Natural Gas Pressures of 0.5 psig or Less

NOTICE

USA boilers built for installation at altitudes greater than 2,000 feet above sea level have been specially orificed

to reduce gas input rate 4 percent per 1,000 feet above sea level per the National Fuel Gas Code, NFPA 54/

ANSI Z223.1. Canadian boilers' orifice sizing is indicated on the rating label. High altitude boiler models are

identifiable by the third digit in the model number suffix on the rating label:

_IN_ _ _ - _ _ 2 less than 2000 ft. elevation

_IN_ _ _ - _ _ 4 2000 to 4500 ft. elevation (Canada)

_IN_ _ _ - _ _ 5 2000 to 5000 ft. elevation (USA)

Fitting

Nominal Pipe Size

½

¾

1

45° Ell

0.7

1.0

1.2

1.6

90° Ell

1.6

2.1

2.6

3.5

Tee

(As Elbow)

3.1

4.1

5.2

6.9

Specific

Gravity

Correction

Factor

Specific

Gravity

Correction

Factor

0.50

1.10

1.30

1.07

0.55

1.04

1.40

1.04

0.60

1.00

1.50

1.00

0.65

0.96

1.60

0.97

0.70

0.93

1.70

0.94

0.75

0.90

0.80

0.87

Length\

[Feet]

0.3 inch w.c. Pressure Drop

0.5 inch w.c. Pressure Drop

½

¾

1

½

¾

1

10

132

278

520

1,050

175

360

680

1,400

20

92

190

350

730

120

250

465

950

30

73

152

285

590

97

200

375

770

40

63

130

245

500

82

170

320

660

50

56

115

215

440

73

151

285

580

60

50

105

195

400

66

138

260

530

70

46

96

180

370

61

125

240

490

80

43

90

170

350

57

118

220

460

90

40

84

160

320

53

110

205

430

100

38

79

150

305

50

103

195

400

DANGER

Doe not use matches, candles, open flames or

other ignition source to check for leaks.