beautypg.com

Burnham Independence IN10 User Manual

Page 61

background image

61

1. Boiling Out of Boiler and System. Oil and grease

which accumulate in a new hot water boiler can be

washed out in the following manner.
a. Remove Safety Relief Valve using extreme care

to avoid damaging it.

b. Partially fill boiler. Pour recommended

compound into boiler through safety relief valve

opening.

c. Replace Safety Relief Valve.
d. Fill entire system with water.
e. Start firing equipment.
f. Circulate the water through the entire system.
g. Vent the system, including the radiation.
h. Allow boiler water to reach operating

temperature, if possible.

i. Continue to Circulate the water for a few hours.
j. Stop the firing equipment.
k. Drain the system in a manner and to a location

that hot water can be discharged with safety.

l. Remove plugs from all available returns and

wash the water side of the boiler as thoroughly as

possible, using a high-pressure water stream.

m. Refill the system with fresh water.
n. Add recommended boiler water treatment.

2. Make pH or Alkalinity Test.

a. After boiler and system have been cleaned and

refilled as previously described, test the pH of

the water in the system. This can easily be done

by drawing a small sample of boiler water and

testing with Hydrion paper which is used in the

same manner as litmus paper, except it gives

specific readings. A color chart on the side of the

small Hydrion dispenser gives the reading in pH.

Hydrion paper is inexpensive and obtainable

from any chemical supply house or through your

local druggist. The pH should be higher than 7

but lower than 11. Add recommended water

treatment chemicals, if necessary, to bring the pH

within the specified range. With this lower level

of protection, care must be exercised to eliminate

all of the free oxygen in the system.

b. Boiler is now ready to be put into service.

CONDENSATION — Following a cold start,

condensation (sweating) may occur in a gas fired

boiler to such an extent that it appears that the boiler

is leaking. This condensation can be expected to

stop after the boiler is hot.

O.

Check Damper Operation - If boiler is equipped with

vent damper, vent damper must be in open position

when boiler main burners are operating. Start boiler,

refer to instructions on damper to determine if damper

is in full open position.

P.

Review User's Information Manual and system

operation with owner or operator.

Q.

Post instructions near boiler for reference by owner

and service personnel. Maintain instructions in legible

condition.