beautypg.com

Bryant 345MAV User Manual

Page 6

background image

II.

UPFLOW APPLICATIONS

An upflow furnace application is where furnace blower is located
below combustion and controls section of furnace, and conditioned
air is discharged upwards.

A.

Condensate Trap Location (Factory-Shipped

Orientation)

The condensate trap is factory installed in the blower shelf and
factory connected for UPFLOW applications. A factory-supplied
tube is used to extend the condensate trap drain connection to the
desired furnace side for field drain attachment. See Condensate
Trap Tubing (Factory-Shipped Orientation) section for drain tube
extension details. (See Fig. 6.)

B.

Condensate Trap Tubing (Factory-Shipped

Orientation)

NOTE:

See Fig. 6 or tube routing label on main furnace door to

confirm location of these tubes.

1. Collector Box Drain, Inducer Housing Drain, Relief Port,

and Pressure Switch Tubes

These tubes are factory attached to the condensate trap and
pressure switch ready for use in UPFLOW applications.
These tubes can be identified by their connection location
and also by a color label on each tube. These tubes are
identified as follows: collector box drain tube (blue label),
inducer housing drain tube (violet label or molded), relief
port tube (green label), and pressure switch tube (pink
label).

2. Condensate Trap Drain Tube

The condensate trap drain connection must be extended for
field attachment by doing the following:
a. Determine location of field drain connection. (See Fig. 2

or 6.)

NOTE:

If internal filter is used, drain tube should be located to

opposite side of casing from return duct attachment to assist in
filter removal.

b. Remove and discard casing drain hole plug button from

desired side.

c. Install drain tube coupling grommet (factory-supplied in

loose parts bag) in selected casing hole.

d. Slide drain tube coupling (factory-supplied in loose parts

bag) through grommet ensuring long end of coupling
faces blower.

e. Cement 2 factory-supplied 1/2-in. street CPVC elbows to

the rigid drain tube connection on the condensate trap.
(See Fig. 6.) These elbows must be cemented together
and cemented to condensate trap drain connection.

NOTE:

Failure to use CPVC elbows may allow drain to kink and

prevent draining.

f. Connect larger diameter drain tube and clamp (factory-

supplied in loose parts bag) to condensate trap and clamp
securely.

g. Route tube to coupling and cut to appropriate length.

h. Attach tube to coupling and clamp securely.

Fig. 6—Factory-Shipped Upflow Tube Configuration

(Shown With Blower Access Panel Removed)

A94163

COLLECTOR BOX

TUBE (PINK)

COLLECTOR BOX

TUBE (GREEN)

INDUCER HOUSING

(MOLDED) DRAIN

TUBE (BEHIND

COLLECTOR BOX

DRAIN TUBE)

COLLECTOR BOX

DRAIN TUBE (BLUE)

FIELD-INSTALLED

FACTORY-SUPPLIED

DRAIN TUBE

COUPLING (LEFT

DRAIN OPTION)

FIELD-INSTALLED

FACTORY-SUPPLIED

DRAIN TUBE

FIELD-INSTALLED

FACTORY-SUPPLIED

1

2

-IN. CPVC STREET

ELBOWS (2) FOR

LEFT DRAIN OPTION

FIELD-INSTALLED

FACTORY-SUPPLIED

DRAIN TUBE

COUPLING (RIGHT

DRAIN OPTION)

CAP

COLLECTOR BOX

DRAIN TUBE (BLUE

& WHITE STRIPED)

PLUG

CONDENSATE
TRAP

Fig. 7—Alternate Upflow Tube Configuration and

Trap Location

A94164

COLLECTOR BOX

TUBE (PINK)

CONDENSATE

TRAP

COLLECTOR BOX

TUBE (GREEN)

COLLECTOR BOX

DRAIN TUBE (BLUE)

INDUCER

HOUSING

DRAIN TUBE

(VIOLET)

CAP

COLLECTOR BOX

DRAIN TUBE (BLUE

& WHITE STRIPED)

PLUG

—6—