beautypg.com

Bryant 345MAV User Manual

Page 31

background image

16. Use appropriate methods to seal openings where vent pipe

passes through roof or sidewall.

D.

Extended Exposed Sidewall Pipes

Sidewall vent pipe termination may be extended beyond area
shown in Fig. 40 and in outside ambient by insulating pipe as
indicated in Table 7.

1. Determine vent pipe diameter, as stated above, using total

pipe length and number of elbows.

2. Find appropriate temperature for your application and

furnace model using winter design temperature (used in
load calculations).

3. Determine required insulation thickness for exposed pipe

lengths.

NOTE:

Pipe length (ft) specified for maximum pipe lengths

located in unconditioned spaces cannot exceed total allowable pipe
length as specified in Table 6.

E.

Vent Termination

Vent pipe must terminate either through roof or sidewall. See
Table 8 for required clearances. See Fig. 39, 40, and 41 for exterior
piping arrangements.

F.

Multiventing

When 2 or more 345MAV Furnaces are vented near each other,
each furnace must be individually vented. NEVER common vent
or breach vent 345MAV furnaces.

VII.

CONDENSATE DRAIN

A.

General

Condensate trap is shipped installed in the blower shelf and factory
connected for UPFLOW applications. Condensate trap must be
RELOCATED for use in DOWNFLOW and HORIZONTAL
applications.

Fig. 34—Combustion-Air and Vent Pipe Connections

CAUTION:

Make sure there is adequate clearance (3-in.

minimum) to any fixed or loose objects in order to ensure
an adequate combustion-air supply. Failure to follow this
caution will result in intermittent unit operation or per-
formance satisfaction.

A96188

COMBUSTION-
AIR

COMBUSTION-

AIR

AIR

FLOW

VENT

VENT

VENT

AIR

FLOW

AIR

FLOW

AIR

FLOW

UPFLOW

DOWNFLOW

HORIZONTAL-LEFT DISCHARGE

HORIZONTAL-RIGHT DISCHARGE

Select 1 vent pipe connection and
1 combustion-air pipe connection.

COMBUSTION-

AIR

COMBUSTION-

AIR

COMBUSTION-

AIR

COMBUSTION-

AIR

NOTE:

Select 1 vent pipe connection and
1 combustion-air pipe connection.

NOTE:

VENT

VENT

VENT

Fig. 35—Combustion-Air Inlet Pipe Assembly

LENGTH OF STRAIGHT PIPE PORTION OF

COMBUSTION-AIR INLET PIPE ASSEMBLY (IN.)

CASING WIDTH

A

17-1/2

8-1/2

±

1/2

21

10-1/2

±

1/2

24-1/2

12

±

1/2

A96211

FIELD-SUPPLIED
2-IN. DIAMETER
PVC PIPE

FIELD-SUPPLIED
2-IN. DIAMETER
PVC 90

°

ELBOW

COMBUSTION-AIR DISC
(FACTORY-SUPPLIED IN
LOOSE PARTS BAG)

A

Fig. 36—Air Intake Housing Plug Fitting Drain

A96190

COMBUSTION–
AIR PIPE

BURNER
BOX

COMBUSTION–AIR
INTAKE HOUSING

3/8

ID TUBE

TRAP

TO OPEN

DRAIN

3/16

DRILL

HOUSING

PLUG

4

MIN

Fig. 37—Vent Pipe Diameter Transition Location and

Elbow Configuration

A93034

FURNACE

PIPE DIAMETER

TRANSITION IN

VERTICAL SECTION

NOT IN
HORIZONTAL
SECTION

—31—