a. Permanently install perforated disk assembly (factory-
supplied in loose parts bag) in combustion-air elbow
using RTV or by cementing. (See Fig. 35.)
For 120,000 Btuh size units only: Separate the 2 halves
of perforated disk assembly and use only the shouldered
disk half.
b. Determine length of straight portion of combustion-air
inlet pipe from table in Fig. 35.
c. Cut field-supplied 2-in diameter PVC pipe to determined
length.
d. Permanently attach elbow/perforated disk assembly to
straight portion of pipe using RTV or by cementing. (See
Fig. 35.)
TABLE 6—MAXIMUM ALLOWABLE PIPE LENGTH (FT) (CONTINUED)
ALTITUDE (FT)
UNIT SIZE
TERMINATION
TYPE
PIPE DIA
(IN.)*
NUMBER OF 90° ELBOWS
1
2
3
4
5
6
4001 to 5000‡
024040
036040
2 Pipe or 2-in
Concentric
1-1/2
60
55
50
45
44
39
2
70
70
70
70
70
70
024060
036060
048060
2 Pipe or 2-in
Concentric
1-1/2
15
10
5
NA
NA
NA
2
64
59
58
53
52
52
036080
048080
060080
2 Pipe or 2-in
Concentric
2
44
39
26
21
20
11
2-1/2
70
70
70
70
70
70
048100
060100
2 Pipe or 3-in
Concentric
2-1/2
31
22
13
12
NA
NA
3
70
70
67
62
57
52
060120
2 Pipe or 3-in.
Concentric
3† no disk
53
46
40
33
26
20
4† no disk
70
70
70
70
70
70
ALTITUDE (FT)
UNIT SIZE
TERMINATION
TYPE
PIPE DIA
(IN.)*
NUMBER OF 90° ELBOWS
1
2
3
4
5
6
5001 to 6000‡
024040
036040
2 Pipe or 2-in
Concentric
1-1/2
57
52
47
42
40
35
2
70
70
70
70
70
70
024060
036060
048060
2 Pipe or 2-in
Concentric
1-1/2
14
9
NA
NA
NA
NA
2
60
55
54
49
48
47
036080
048080
060080
2 Pipe or 2-in
Concentric
2
41
36
23
18
17
8
2-1/2
70
70
70
70
70
70
048100
060100
2 Pipe or 3-in
Concentric
2-1/2
29
21
12
11
NA
NA
3
70
67
62
57
52
47
060120
2 Pipe or 3-in.
Concentric
3† no disk
42
35
29
22
15
9
4† no disk
70
70
70
70
70
70
ALTITUDE (FT)
UNIT SIZE
TERMINATION
TYPE
PIPE DIA
(IN.)*
NUMBER OF 90° ELBOWS
1
2
3
4
5
6
6001 to 7000‡
024040
036040
2 Pipe or 2-in
Concentric
1-1/2
53
48
43
38
37
32
2
70
70
68
67
66
64
024060
036060
048060
2 Pipe or 2-in
Concentric
1-1/2
13
8
NA
NA
NA
NA
2
57
52
50
45
44
43
036080
048080
060080
2 Pipe or 2-in
Concentric
2
38
33
21
16
15
6
2-1/2
70
70
68
67
66
64
048100
060100
2 Pipe or 3-in
Concentric
2-1/2
27
19
10
9
NA
NA
3
68
63
58
53
48
43
060120
2 Pipe or 3-in.
Concentric
3† no disk
31
24
18
11
NA
NA
4† no disk
70
70
70
70
67
62
ALTITUDE (FT)
UNIT SIZE
TERMINATION
TYPE
PIPE DIA
(IN.)*
NUMBER OF 90° ELBOWS
1
2
3
4
5
6
7001 to 8000‡
024040
036040
2 Pipe or 2-in
Concentric
1-1/2
49
44
39
34
33
28
2
66
65
63
62
60
59
024060
036060
048060
2 Pipe or 2-in
Concentric
1-1/2
12
7
NA
NA
NA
NA
2
53
48
46
41
40
38
036080
048080
060080
2 Pipe or 2-in
Concentric
2
36
31
19
14
12
NA
2–1/2
66
65
63
62
60
59
048100
060100
2 Pipe or 3-in
Concentric
2–1/2
25
17
8
7
NA
NA
3
63
58
53
48
43
38
060120
2 Pipe or 3-in.
Concentric
3† no disk
20
13
7
NA
NA
NA
4† no disk
61
56
51
46
41
36
See notes at end of table
—26—