A. Technical appendix

A−29

Festo P.BE−SFC−DC−PB−S7−E N en 0604NH

Station status 1

Bit 3 is especially of interest with station status 1. If this bit is
set, it is sensible to evaluate the device−related diagnosis.

Station status 1

Bit

Meaning

Explanation

0

Diag.Station_Non_Existent

SFC−DC no longer/not yet addressable.
Possible causes:
Ĉ Operating voltage not applied
Ĉ Data cable interrupted
Ĉ Fault in data cable

1

Diag.Station_Not_Ready

SFC−DC not yet ready for data exchange

2

Diag.Cfg_Fault

The configuration data received from the master are not
the same as those ascertained by the SFC−DC.

3

Diag.Ext_Diag

There is a device−related diagnosis.

1)

4

Diag.Not_Supported

1 = The SFC−DC does not support the function requested.

5

Diag.Invalid_Slave_Response

Always 0 (always reset to 0 by the SFC−DC)

2)

6

Diag.Prm_Fault

Last parametrizing telegram faulty

7

Diag.Master_Lock

Access by a different master (set by the master)

1)

Is set by the SFC−DC when a new fault occurs (new fault message).

2)

Is set to 1 in the DP master when the reply sent by the slave cannot be interpreted.

Tab. A/17:

Structure of station status 1